Bryant manual UNIT 524J

Models: 524J

1 36
Download 36 pages 19.5 Kb
Page 4
Image 4
Manual background

524J

Table 1B —524J***A Physical Data, SI — Cooling Units

UNIT 524J*

25A

 

28A

 

30A

NOMINAL CAPACITY (kW)

70

 

87

 

105

 

 

 

 

 

 

OPERATING WEIGHT (kg)

 

 

 

 

 

Base Unit with TXV

331

 

477

 

482

Plenum

102

 

148

 

148

 

 

 

 

 

 

FANS

 

 

 

 

 

Qty...Diam. (mm)

2...381

 

2...457

 

2...457

Nominal Airflow (L/s)

3775

 

4119

 

5663

Airflow Range (L/s)

2831 – 4719

 

3539 – 5899

 

4247 – 7079

Nominal Motor kW (Standard Motor)

 

 

 

 

 

208/230---3---60 and 460---3---60

3.73

 

5.60

 

7.46

575---3---60

3.73

 

5.60

 

7.46

Motor Speed (r/s)

 

 

 

 

 

208/230---3---60 and 460---3---60

29.1

 

29.1

 

29.1

575---3---60

29.1

 

29.3

 

29.3

 

 

 

 

 

 

REFRIGERANT

 

 

R--- 410A

 

Operating charge (kg)

1.59

 

2.04

 

2.27

(approx per circuit)*

 

 

 

 

 

 

 

 

 

 

 

 

DIRECT---EXPANSION COIL

Enhanced Copper Tubes, Aluminum Sine--- Wave Fins

Max Working Pressure (kPag)

 

4481

 

 

Face Area (sq m)

1.85

 

 

2.77

 

2.30

 

No. of Splits

2

 

2

 

2

No. of Circuits per Split

18

 

20

 

24

Split Type...Percentage

 

 

Face...50/50

 

Rows...Fins/m

4...591

 

 

4...591

 

4...591

 

 

 

 

 

 

 

PIPING CONNECTIONS,

 

 

 

 

 

Quantity...Size (in.)

 

 

 

 

 

DX Coil — Suction (ODF)

2...11/8

 

2...13/8

 

2...13/8

 

 

DX Coil — Liquid Refrigerant (ODF)

 

 

2...5/8

 

 

Steam Coil, In (MPT)

 

1...21/2

 

 

Steam Coil, Out (MPT)

 

1...1/2

 

 

Hot Water Coil, In (MPT)

 

1...2

 

 

Hot Water Coil, Out (MPT)

 

1...2

 

 

Condensate (PVC)

 

 

1...11/4 ODM/1 IDF

 

FILTERS

Throwaway — Factory Supplied

Quantity...Size (mm.)

4...406 x 508 x 51

 

4...508 x 610 x 51

 

4...406 x 610 x 51

 

4...508 x 635 x 51

 

 

Access Location

 

 

Either Side

 

 

 

 

 

 

 

STEAM COIL**

 

 

 

 

 

Max Working Pressure (kPag at 126° C)

 

138

 

 

Total Face Area (sq m)

1.24

 

 

1.39

 

1.39

 

Rows...Fins/m

1...394

 

1...394

 

1...394

 

 

 

 

 

 

HOT WATER COIL**

 

 

 

 

 

Max Working Pressure (kPag)

 

1034

 

 

Total Face Area (sq m)

1.24

 

 

1.39

 

1.39

 

Rows...Fins/m

2...335

 

2...335

 

2...335

Water Volume

 

 

 

 

 

(L)

52.6

 

 

 

54.1

 

(m3)

0.052

 

0.054

 

LEGEND

DX — Direct Expansion

TXV — Thermostatic Expansion Valve

*Units are shipped without refrigerant charge.