Bryant 524J manual E - Medium-StaticDrive Data, 60 Hz - SI, F - High-StaticDrive Data, 60 Hz - SI

Models: 524J

1 36
Download 36 pages 19.5 Kb
Page 27
Image 27
Table 9E - Medium-Static Drive Data, 60 Hz — SI

Table 9E - Medium-Static Drive Data, 60 Hz — SI

UNIT

524J*25A

524J*28A

524J*30A

524J*25H

 

 

 

 

 

 

 

MOTOR DRIVE

 

 

 

 

 

 

 

Motor Pulley Pitch Diameter (mm)

109.2--- 134.6

109.2--- 134.6

109.2--- 134.6

 

 

 

 

Pulley Factory Setting

3.0

3.0

3.0

Full Turns Open

 

 

 

 

 

 

 

FAN DRIVE

 

 

 

 

 

 

 

Pulley Pitch Dia (mm)

239

239

239

 

 

 

 

Pulley Bore (mm)

36.5

49.2

49.2

 

 

 

 

Belt No. — Section

1—B

2—B

2—B

Belt Pitch (mm)

1062

(2) 986

(2) 986

(2) 1011

(2) 1011

 

 

 

 

 

 

FAN SPEEDS (r/s)

 

 

 

 

 

 

 

Factory Setting

14.7

14.7

14.7

 

 

 

 

Range

13.3--- 16.4

13.3--- 16.4

13.3--- 16.4

 

 

 

 

Max Allowable Speed (r/s)

20.0

18.3

18.3

 

 

 

 

Change per 1/ Turn of

 

 

 

2

0.255

0.255

0.255

Moveable Motor Pulley

Flange

 

 

 

 

 

 

 

MAX FULL TURNS FROM

6

6

6

CLOSED POSITION

 

 

 

 

 

 

 

SHAFTS CENTER DISTANCE (mm)

232--- 279

169--- 240

169--- 240

 

 

 

 

Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

Table 9F - High-Static Drive Data, 60 Hz — SI

UNIT

524J*25A

524J*28A

524J*30A

524J*25H

 

 

 

 

 

 

 

MOTOR DRIVE

 

 

 

 

 

 

 

Motor Pulley Pitch Diameter (mm)

109.2--- 134.6

109.2--- 134.6

109.2--- 134.6

 

 

 

 

Pulley Factory Setting

3.0

3.0

3.0

Full Turns Open

 

 

 

 

 

 

 

FAN DRIVE

 

 

 

 

 

 

 

Pulley Pitch Dia (mm)

188

203

203

Pulley Bore (mm)

36.5

49.2

49.2

 

 

 

 

Belt No. — Section

2—B

2—B

2—B

 

 

 

 

Belt Pitch (mm)

935

935

960

 

 

 

 

FAN SPEEDS (r/s)

 

 

 

 

 

 

 

Factory Setting

18.6

17.1

17.1

 

 

 

 

Range

16.9--- 20.0

14.6--- 17.9

14.6--- 7.9

Max Allowable Speed (r/s)

20.0

18.3

18.3

 

 

 

 

Change per 1/ Turn of

 

 

 

2

0.323

0.278

0.278

Moveable Motor Pulley

Flange

 

 

 

 

 

 

 

MAX FULL TURNS FROM

6

6

6

CLOSED POSITION

 

 

 

 

 

 

 

SHAFTS CENTER DISTANCE (mm)

207--- 255

169--- 240

169--- 240

 

 

 

 

It is possible to adjust drive so that fan speed exceeds maximum allowable. DO NOT exceed 20 r/s

524J

27

Page 27
Image 27
Bryant 524J manual E - Medium-StaticDrive Data, 60 Hz - SI, F - High-StaticDrive Data, 60 Hz - SI