Bryant manual UNIT 524J

Models: 524J

1 36
Download 36 pages 19.5 Kb
Page 3
Image 3
UNIT 524J*

Table 1A — 524J***A Physical Data, English — Cooling Units

UNIT 524J*

25A

 

28A

 

30A

NOMINAL CAPACITY (Tons)

20

 

25

 

30

 

 

 

 

 

 

OPERATING WEIGHT (lb)

 

 

 

 

 

Base Unit with TXV

730

 

1050

 

1062

Plenum

225

 

325

 

325

 

 

 

 

 

 

FANS

 

 

 

 

 

Qty...Diam. (in.)

2...15

 

2...18

 

2...18

Nominal Airflow (cfm)

8000

 

10000

 

12000

Airflow Range (cfm)

6000 – 10000

 

7500 – 12500

 

9000 – 15000

Nominal Motor Hp (Standard Motor)

 

 

 

 

 

208/230---3---60 and 460---3---60

5.0

 

7.5

 

10.0

575---3---60

5.0

 

7.5

 

10.0

Motor Speed (rpm)

 

 

 

 

 

208/230---3---60 and 460---3---60

1745

 

1745

 

1745

575---3---60

1745

 

1755

 

1755

 

 

 

 

 

 

REFRIGERANT

 

 

R--- 410A

 

Operating charge (lb)

3.5

 

4.5

 

5.0

(approx per circuit)*

 

 

 

 

 

 

 

 

 

 

 

 

DIRECT---EXPANSION COIL

Enhanced Copper Tubes, Aluminum Sine--- Wave Fins

Max Working Pressure (psig)

 

650

 

 

Face Area (sq ft)

19.88

 

 

29.83

 

24.86

 

No. of Splits

2

 

2

 

2

No. of Circuits per Split

18

 

20

 

24

Split Type...Percentage

 

 

Face...50/50

 

Rows...Fins/in.

4...15

 

 

4...15

 

4...15

 

 

 

 

 

 

 

PIPING CONNECTIONS,

 

 

 

 

 

Quantity...Size (in.)

 

 

 

 

 

DX Coil — Suction (ODF)

2...11/8

 

2...13/8

 

2...13/8

 

 

DX Coil — Liquid Refrigerant (ODF)

 

 

2...5/8

 

 

Steam Coil, In (MPT)

 

1...21/2

 

 

Steam Coil, Out (MPT)

 

1...1/2

 

 

Hot Water Coil, In (MPT)

 

1...2

 

 

Hot Water Coil, Out (MPT)

 

1...2

 

 

Condensate (PVC)

 

 

1...11/4 ODM/1 IDF

 

FILTERS

Throwaway — Factory Supplied

Quantity...Size (in.)

4...16 x 20 x 2

 

4...20 x 24 x 2

 

4...16 x 24 x 2

 

4...20 x 25 x 2

 

 

Access Location

 

 

Either Side

 

 

 

 

 

 

 

STEAM COIL**

 

 

 

 

 

Max Working Pressure (psig at 260° F)

 

20

 

 

Total Face Area (sq ft)

13.33

 

 

15.0

 

15.0

 

Rows...Fins/in.

1...10

 

1...10

 

1...10

 

 

 

 

 

 

HOT WATER COIL**

 

 

 

 

 

Max Working Pressure (psig)

 

150

 

 

Total Face Area (sq ft)

13.33

 

 

15.0

 

15.0

 

Rows...Fins/in.

2...8.5

 

2...12.5

 

2...12.5

Water Volume

 

 

 

 

 

(gal)

13.9

 

 

 

14.3

 

(ft3)

 

 

1.90

 

LEGEND

DX — Direct Expansion

TXV — Thermostatic Expansion Valve

*Units are shipped without refrigerant charge.

**Field installed accessory only.

524J

3

Page 3
Image 3
Bryant manual UNIT 524J