DETAILED COOLING CAPACITIES* Continued

EVAP

 

 

 

 

 

CONDENSER ENTERING AIR TEMPERATURES °F

 

 

 

 

AIR

75

 

85

 

95

 

105

 

 

115

 

125

 

 

 

Capacity

Total

Capacity

Total

Capacity

Total

Capacity

Total

 

Capacity

Total

Capacity

Total

 

 

MBtuh†

MBtuh†

MBtuh†

MBtuh†

 

MBtuh†

MBtuh†

 

 

Sys

Sys

Sys

Sys

 

Sys

Sys

CFM

EWB

Total

Sens‡

Kw**

Total

Sens‡

Kw**

Total

Sens‡

Kw**

Total

Sens‡

Kw**

Total Sens‡

Kw**Total Sens‡

Kw**

533AN036-A Outdoor Section With CK5AA042 Indoor Section

 

72

40.6

20.1

2.70

39.1

19.6

3.00

37.3

19.0

3.33

35.3

18.3

3.70

33.0

17.6

4.08

30.5

16.8

4.52

1050

67

38.2

26.3

2.68

36.3

25.5

2.98

34.5

24.8

3.30

32.4

24.0

3.66

30.2

23.2

4.04

26.5

21.9

4.43

63††

35.9

25.8

2.67

34.1

25.1

2.96

32.0

24.1

3.27

29.6

23.1

3.62

26.8

21.9

3.97

23.4

20.5

4.35

 

62

35.4

32.2

2.67

32.6

30.8

2.94

29.7

29.4

3.24

28.2

28.2

3.59

26.8

26.8

3.98

24.9

24.9

4.39

 

57

33.6

33.6

2.64

31.7

31.7

2.92

29.6

29.6

3.23

28.3

28.3

3.59

26.9

26.9

3.98

24.6

24.6

4.38

 

72

41.1

20.8

2.76

39.6

20.3

3.06

37.8

19.8

3.40

35.7

19.2

3.76

33.4

18.4

4.15

30.8

17.7

4.59

1200

67

38.9

27.8

2.75

36.9

27.0

3.04

35.0

26.4

3.37

32.9

25.6

3.72

30.6

24.9

4.11

26.9

23.5

4.50

63††

36.6

27.4

2.73

34.7

26.6

3.02

32.5

25.7

3.34

30.1

24.7

3.68

27.2

23.5

4.04

23.7

22.0

4.42

 

62

36.2

34.5

2.73

33.4

33.0

3.00

31.7

31.7

3.32

30.2

30.2

3.68

28.7

28.7

4.07

25.9

25.9

4.47

 

57

35.0

35.0

2.71

33.9

33.9

3.01

31.8

31.8

3.32

30.5

30.5

3.69

29.0

29.0

4.08

25.9

25.9

4.47

 

72

41.4

21.4

2.82

39.9

21.0

3.13

38.1

20.5

3.46

36.0

19.9

3.82

33.7

19.2

4.22

31.0

18.6

4.65

1350

67

39.1

29.0

2.80

37.4

28.5

3.10

35.4

27.8

3.43

33.3

27.1

3.78

31.0

26.5

4.18

27.5

25.1

4.58

63††

37.0

28.8

2.79

35.2

28.1

3.08

32.9

27.1

3.40

30.4

26.1

3.74

27.5

24.9

4.11

24.1

23.4

4.49

 

62

37.0

36.5

2.79

35.4

35.4

3.09

33.6

33.6

3.41

31.8

31.8

3.76

29.8

29.8

4.16

26.7

26.7

4.56

 

57

36.9

36.9

2.79

35.4

35.4

3.09

33.7

33.7

3.41

31.8

31.8

3.76

29.8

29.8

4.16

27.0

27.0

4.56

Multipliers for Determining the Performance With Other Indoor Sections

 

Indoor

 

 

Cooling

Indoor

 

 

Cooling

 

 

Section

Size

Capacity

 

Power

Section

Size

Capacity

 

Power

 

 

CC5A/CD5AA

036

1.00

 

1.00

COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE

 

 

 

042

1.00

 

1.00

CC5A/CD5AA

042

0.99

 

0.92

 

 

CC5A/CD5AW

036

1.00

 

1.00

CC5A/CD5AW

036

0.99

 

0.92

 

 

 

042

0.99

 

1.00

CK5A/CK5BA

042

0.99

 

0.92

 

 

CE3AA

036

0.99

 

1.00

CK5A/CK5BW

036

0.99

 

0.92

 

 

 

042

1.00

 

1.00

COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE

 

 

CF5AA

036

0.99

 

1.00

CC5A/CD5AA

042

0.99

 

0.92

 

 

CK3BA

036

1.00

 

1.00

CC5A/CD5AW

036

0.99

 

0.92

 

 

 

042

1.00

 

1.00

CK5A/CK5BA

042

0.99

 

0.92

 

 

CK5A/CK5BA

036

1.00

 

1.00

CK5A/CK5BW

036

0.99

 

0.92

 

 

CK5A/CK5BN

042

1.00

 

1.00

COILS + 355MAV042040 VARIABLE SPEED FURNACE

 

 

CK5A/CK5BT

036

1.00

 

1.00

CC5A/CD5AA

042

0.99

 

0.93

 

 

 

042

1.00

 

1.00

CC5A/CD5AW

036

0.99

 

0.94

 

 

CK5A/CK5BW

036

1.00

 

1.00

CK5A/CK5BA

042

0.99

 

0.93

 

 

F(A,B)4AN(F,B,C)

042

1.00

 

1.01

CK5A/CK5BW

036

0.99

 

0.94

 

 

F(A,B)4AN(F,C)

036

0.97

 

1.02

COILS + 355MAV042060 VARIABLE SPEED FURNACE

 

 

FC4BN(F,B)

042

1.00

 

1.00

CC5A/CD5AA

036

0.99

 

0.94

 

 

FCBNF

036

0.97

 

1.01

CK3BA

036

0.99

 

0.94

 

 

FG3AAA

036

0.97

 

1.00

CK5A/CK5BA

036

0.99

 

0.94

 

 

FK4CNB

006

1.01

 

0.90

COILS + 355MAV042080 VARIABLE SPEED FURNACE

 

 

FK4CNF

001

0.97

 

0.94

CC5A/CD5AA

042

0.99

 

0.93

 

 

 

002

0.97

 

0.94

CC5A/CD5AW

036

0.99

 

0.93

 

 

 

003

0.98

 

0.91

 

042

0.99

 

0.93

 

 

 

005

1.00

 

0.91

CK5A/CK5BA

042

0.99

 

0.93

 

 

FV4ANB

006

1.02

 

0.90

CK5A/CK5BW

036

0.99

 

0.93

 

 

FV4ANF

002

0.97

 

0.94

COILS + 355MAV060080 VARIABLE SPEED FURNACE

 

 

 

003

0.98

 

0.91

CC5A/CD5AA

042

0.99

 

0.93

 

 

 

005

1.00

 

0.91

CC5A/CD5AW

036

0.99

 

0.94

 

 

FX4ANF

042

0.97

 

1.00

 

042

0.99

 

0.93

 

 

COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE

CK5A/CK5BA

042

0.99

 

0.94

 

 

CC5A/CD5AA

036

0.99

 

0.95

CK5A/CK5BW

036

0.99

 

0.94

 

 

CK3BA

036

0.99

 

0.95

COILS + 355MAV060100 VARIABLE SPEED FURNACE

 

 

CK5A/CK5BA

036

0.99

 

0.95

CC5A/CD5AA

042

0.99

 

0.92

 

 

COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE

CC5A/CD5AW

036

0.99

 

0.92

 

 

CC5A/CD5AA

042

0.99

 

0.93

 

042

0.99

 

0.92

 

 

CC5A/CD5AW

036

0.99

 

0.94

CK5A/CK5BA

042

0.99

 

0.92

 

 

 

042

0.99

 

0.93

CK5A/CK5BW

036

0.99

 

0.92

 

 

CK3BA

042

0.99

 

0.93

COILS + 355MAV060120 VARIABLE SPEED FURNACE

 

 

CK5A/CK5BA

042

0.99

 

0.93

CC5A/CD5AA

042

0.99

 

0.92

 

 

CK5A/CK5BW

036

0.99

 

0.94

CC5A/CD5AW

036

0.99

 

0.92

 

 

 

 

CK5A/CK5BA

042

0.99

 

0.92

 

 

 

 

 

 

 

CK5A/CK5BW

036

0.99

 

0.92

 

See notes on page 19.

—16—

Page 16
Image 16
Bryant warranty 533AN036-A Outdoor Section With CK5AA042 Indoor Section, Coils + 333B,JAV048080 Variable Speed Furnace