SPECIFICATIONS Continued

SPECIFICATIONS Continued

UNIT SIZE-SERIES

042-A/A

 

048-A/A

060-A/A

 

 

 

 

 

 

 

 

Operating Weight (Lb)

197

 

203

238

 

 

 

 

 

 

 

 

ELECTRICAL

 

 

 

 

Unit Volts—Hertz—Phase

 

 

208/230—60—1/208/230—60—3

 

 

 

 

 

 

 

 

 

Operating Voltage Range*

 

 

187—253/197—253

 

 

 

 

 

 

 

 

Compressor—Rated Load Amps

18.6/13.5

 

20.5/14.7

27.6/18.1

 

 

 

 

 

 

 

 

 

 

 

Locked Rotor Amps

105.0/77.0

 

109.0/91.0

158.0/137.0

 

 

 

 

 

 

 

 

Condenser Fan Motor—Full Load Amps

1.1

 

1.4

1.4

 

 

 

 

 

 

 

 

Min Unit Ampacity for Wire Sizing

24.4/18.0

 

27.0/19.8

35.9/24.0

 

 

 

 

 

 

 

 

Min Wire Size (60°C Copper) AWG†

10/14

 

10/12

8/10

 

 

 

 

 

 

 

 

Min Wire Size (75°C Copper) AWG†

10/14

 

10/12

8/10

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (60°C Copper)‡

81/51

 

74/73

86/96

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (75°C Copper)‡

77/48

 

70/69

82/91

 

 

 

 

 

 

 

 

Max Branch Circuit Fuse or

 

 

 

 

Circuit Breaker Size (Amps)

40/25

 

40/30

60/40

 

 

 

 

 

 

 

 

COMPRESSOR & REFRIGERANT

 

 

 

 

Compressor— Type

 

 

Scroll

 

 

 

 

 

 

 

 

 

 

 

 

Manufacturer

 

 

Copeland

 

 

 

 

 

 

 

 

 

Temperature & Current Protection

 

 

Internal Line Break

 

 

 

 

 

 

 

 

 

Refrigerant—Type

 

 

Puron® (R-410A)

 

 

 

 

 

 

 

 

Amount (Lb)

6.38

 

7.13

9.75

 

 

 

 

 

 

 

 

CONDENSER COIL & FAN

 

 

 

 

Coil Face Area (Sq Ft)

14.8

 

14.8

22.2

 

 

 

 

 

 

 

 

Fins per In.—Rows—Circuits

20—1—2

 

25—1—2

25—1—3

 

 

 

 

 

 

 

 

Fan Motor—HP (PSC) & RPM

1/5 & 825

 

1/4 & 1100

1/4 & 1100

 

 

 

 

 

 

 

 

Volts—Hertz—Phase

 

 

208/230—60—1

 

 

 

 

 

 

 

 

Condenser Airflow (CFM)

2800

 

2800

3300

 

 

 

 

 

 

 

 

OPTIONAL EQUIPMENT

 

 

 

 

Support Feet

 

 

KSASF0101AAA

 

 

 

 

 

 

 

 

 

Coastal Filter

 

 

KAACF1101LRG

 

 

 

 

 

 

 

 

 

Time Delay Relay

 

 

KAATD0101TDR

 

 

 

 

 

 

 

 

 

Cycle Protector

 

 

KSACY0101AAA

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

 

KAACH1201AAA

 

 

 

 

 

 

 

 

Sound Blanket

 

KSASH0601COP

KSASH2101COP

 

 

 

 

 

 

 

Start Assist—Capacitor/Relay Type

 

KSAHS1501AAA/NA

KSAHS1601AAA/NA

 

 

 

 

 

 

 

 

Start Assist—PTC Type

 

 

KAACS0201PTC/NA

 

 

 

 

 

 

 

 

 

TXV (Hard Shutoff)

KSATX0301HSZ

 

KSATX0401HSZ

KSATX0501HSZ

 

 

 

 

 

 

 

 

Piston Body

 

 

KSAPX0101PIS

 

 

 

 

 

 

 

 

 

Filter Drier (Suction Line)

 

 

KH45LG141 (RCD)

 

 

 

 

 

 

 

 

 

Evaporator Freeze Thermostat††

 

 

KAAFT0101AAA

 

 

 

 

 

 

 

 

 

Liquid-Line Solenoid Valve

 

 

KAALS0201LLS

 

 

 

 

 

 

 

 

 

Winter Start Control††

 

 

KAAWS0101AAA

 

 

 

 

 

 

 

 

 

Low-Ambient Pressure Switch

 

 

KSALA0301410

 

 

 

 

 

 

 

 

 

Low-Ambient Controller

 

 

P251-0083 (RCD)

 

 

 

 

 

 

 

 

 

MotorMaster® Control**

 

 

32LT660004 (RCD)

 

 

 

 

 

 

 

 

 

Ball Bearing Fan Motor

 

 

HC38GE231 (RCD)

 

 

 

 

 

 

 

 

 

Thermostat—Auto Changeover,

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBNAC01-B

 

 

 

 

 

 

 

 

 

Thermostat—Auto Changeover,

 

 

 

 

7-Day Programmable, °F/°C,

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBPAC01-B

 

 

 

 

 

 

 

 

 

Thermidistat™ Control—

 

 

 

 

Programmable Thermostat with Humidity Control

 

 

TSTATBBPRH01-B

 

 

 

 

 

 

 

 

 

Builder’s Thermostat—Manual Changeover,

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBBAC01-B

 

 

 

 

 

 

 

 

 

Thermostat, Manual Changeover, 5-2 Day

 

 

 

 

Programmable, °F/°C, 1-Stage heat/1-Stage Cool

 

 

TSTATBBSAC01

 

Outdoor Air Temperature Sensor

 

 

TSTATXXSEN01-B

 

 

 

 

 

 

 

 

 

Backplate for Non-Programmable Thermostat

 

 

TSTATXXNBP01

 

 

 

 

 

 

 

 

 

Backplate for Programmable Thermostat

 

 

TSTATXXPBP01

 

 

 

 

 

 

 

 

 

Backplate for Builder’s Thermostat

 

 

TSTATXXBBP01

 

 

 

 

 

 

 

 

 

Backplate for Standard Programmable

 

 

 

 

Thermostat

 

 

TSTATXXSBP01

 

Thermostat Conversion Kit (4 to 5 wire)—10 Pack

 

 

TSTATXXCNV10

 

 

 

 

 

 

 

 

 

See notes on page 6.