CONDENSER ONLY RATINGS* Continued

SST

 

 

 

CONDENSER ENTERING AIR TEMPERATURES °F

 

 

 

 

 

 

 

 

 

 

 

°F

 

55

65

75

85

95

105

115

125

 

 

 

 

 

 

 

 

 

 

533AN042-A

30

TCG

36.9

35.0

33.0

31.1

29.1

27.1

25.1

22.9

SDT

77.8

87.5

97.2

107.

117.

127.

136.

146.

 

KW

1.90

2.17

2.46

2.80

3.17

3.59

4.07

4.60

 

 

 

 

 

 

 

 

 

 

35

TCG

40.4

38.3

36.2

34.1

32.0

29.9

27.6

25.2

SDT

79.3

88.8

98.5

108.

118.

127.

137.

147.

 

KW

1.93

2.19

2.49

2.82

3.20

3.61

4.08

4.60

 

 

 

 

 

 

 

 

 

 

40

TCG

44.2

41.9

39.7

37.4

35.1

32.8

30.3

27.7

SDT

81.0

90.4

100.0

110.

119.

129.

138.

148.

 

KW

1.97

2.23

2.53

2.86

3.23

3.64

4.11

4.63

 

 

 

 

 

 

 

 

 

 

45

TCG

48.2

45.7

43.3

40.8

38.3

35.8

33.1

30.3

SDT

82.8

92.2

102.

111.

121.

130.

140.

149.

 

KW

2.01

2.27

2.57

2.90

3.27

3.68

4.14

4.66

 

 

 

 

 

 

 

 

 

 

50

TCG

52.4

49.7

47.1

44.4

41.7

39.0

36.1

33.0

SDT

84.9

94.1

103.

113.

122.

132.

141.

150.

 

KW

2.05

2.31

2.61

2.95

3.32

3.73

4.19

4.70

 

 

 

 

 

 

 

 

 

 

55

TCG

56.8

54.0

51.1

48.2

45.3

42.3

39.2

35.8

SDT

87.0

96.1

105.

115.

124.

133.

142.

152.

 

KW

2.11

2.37

2.66

3.00

3.37

3.78

4.24

4.75

 

 

 

 

 

 

 

 

 

 

533AN048-A

30

TCG

42.2

40.0

37.8

35.6

33.4

31.1

28.7

26.2

SDT

76.9

86.5

96.3

106.

116.

126.

136.

146.

 

KW

2.23

2.53

2.87

3.26

3.69

4.17

4.72

5.32

 

 

 

 

 

 

 

 

 

 

35

TCG

46.3

43.9

41.5

39.1

36.7

34.3

31.7

29.0

SDT

78.2

87.7

97.4

107.

117.

127.

137.

146.

 

KW

2.26

2.56

2.90

3.28

3.70

4.18

4.72

5.32

 

 

 

 

 

 

 

 

 

 

40

TCG

50.7

48.1

45.5

42.9

40.3

37.6

34.8

31.8

SDT

79.8

89.2

98.7

108.

118.

128.

137.

147.

 

KW

2.30

2.59

2.93

3.31

3.73

4.21

4.74

5.33

 

 

 

 

 

 

 

 

 

 

45

TCG

55.2

52.5

49.7

46.9

44.0

41.1

38.1

34.9

SDT

81.5

90.8

100.

110.

119.

129.

138.

148.

 

KW

2.35

2.64

2.97

3.35

3.77

4.24

4.77

5.36

 

 

 

 

 

 

 

 

 

 

50

TCG

60.1

57.1

54.1

51.1

48.0

44.9

41.6

38.1

SDT

83.5

92.6

102.

111.

121.

130.

140.

149.

 

KW

2.40

2.69

3.02

3.40

3.82

4.29

4.81

5.40

 

 

 

 

 

 

 

 

 

 

55

TCG

65.1

62.0

58.8

55.5

52.2

48.8

45.2

41.4

SDT

85.6

94.6

104.

113.

122.

132.

141.

151.

 

KW

2.45

2.75

3.08

3.45

3.88

4.34

4.86

5.44

 

 

 

 

 

 

 

 

 

 

533AN060-A

30

TCG

53.6

50.8

48.1

45.3

42.5

39.6

36.5

32.7

SDT

78.4

87.9

97.7

108.

117.

127.

137.

146.

 

KW

2.84

3.22

3.64

4.12

4.65

5.24

5.86

6.46

 

 

 

 

 

 

 

 

 

 

35

TCG

58.7

55.7

52.7

49.7

46.7

43.6

40.3

36.5

SDT

79.9

89.5

99.2

109.

119.

128.

138.

147.

 

KW

2.89

3.26

3.68

4.16

4.70

5.28

5.93

6.59

 

 

 

 

 

 

 

 

 

 

40

TCG

64.0

60.8

57.6

54.3

51.0

47.7

44.2

40.3

SDT

81.8

91.2

101.

110.

120.

130.

139.

149.

 

KW

2.94

3.31

3.74

4.22

4.75

5.34

5.99

6.69

 

 

 

 

 

 

 

 

 

 

45

TCG

69.7

66.3

62.8

59.2

55.6

52.0

48.2

44.0

SDT

83.7

93.1

103.

112.

122.

131.

141.

150.

 

KW

3.00

3.37

3.80

4.28

4.82

5.41

6.06

6.78

 

 

 

 

 

 

 

 

 

 

50

TCG

75.6

72.0

68.2

64.4

60.5

56.5

52.4

47.9

SDT

85.8

95.1

104.

114.

123.

133.

142.

151.

 

KW

3.06

3.44

3.87

4.35

4.89

5.48

6.14

6.85

 

 

 

 

 

 

 

 

 

 

55

TCG

81.9

78.0

74.0

69.9

65.6

61.2

56.8

51.9

SDT

88.1

97.3

107.

116.

125.

135.

144.

153.

 

KW

3.14

3.52

3.95

4.43

4.97

5.57

6.22

6.94

 

 

 

 

 

 

 

 

 

 