Bryant 533A warranty Specifications, Unit Size-Series, 024-A, 030-A/A, 036-A/A, Electrical

Models: 533A

1 24
Download 24 pages 18.21 Kb
Page 4
Image 4
SPECIFICATIONS

SPECIFICATIONS

UNIT SIZE-SERIES

024-A

 

030-A/A

036-A/A

 

 

 

 

 

 

 

 

Operating Weight (Lb)

143

 

138

156

 

 

 

 

 

 

 

 

ELECTRICAL

 

 

 

 

Unit Volts—Hertz—Phase

208/230—60—1

 

208/230—60—1/208/230—60—3

208/230—60—1/208/230—60—3

 

 

 

 

 

 

 

 

Operating Voltage Range*

187—253

 

187—253/197—253

187—253/197—253

 

 

 

 

 

 

 

 

Compressor— Rated Load Amps

13.5

 

14.7/9.6

15.4/12.2

 

 

 

 

 

 

 

 

 

 

 

Locked Rotor Amps

61.0

 

72.5/63.0

83.0/77.0

 

 

 

 

 

 

 

 

Condenser Fan Motor—Full Load Amps

0.50

 

0.80

1.4

 

 

 

 

 

 

 

 

Min Unit Ampacity for Wire Sizing

17.4

 

19.2/12.8

20.7/16.7

 

 

 

 

 

 

 

 

Min Wire Size (60°C Copper) AWG†

14

 

14

12/14

 

 

 

 

 

 

 

 

Min Wire Size (75°C Copper) AWG†

14

 

14

12/14

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (60°C Copper)‡

45

 

41/70

62/54

 

 

 

 

 

 

 

 

Max Wire Length (Ft) (75°C Copper)‡

43

 

39/67

59/51

 

 

 

 

 

 

 

 

Max Branch Circuit Fuse or

 

 

 

 

Circuit Breaker Size (Amps)

25

 

30/20

30/25

 

 

 

 

 

 

 

 

COMPRESSOR & REFRIGERANT

 

 

 

 

Compressor— Type

 

 

Scroll

 

 

 

 

 

 

 

 

 

 

 

 

Manufacturer

 

 

Copeland

 

 

 

 

 

 

 

 

 

Temperature & Current Protection

 

 

Internal Line Break

 

 

 

 

 

 

 

 

 

Refrigerant— Type

 

 

Puron® (R-410A)

 

 

 

 

 

 

 

 

 

 

Amount (Lb)

5.00

 

5.50

5.75

 

 

 

 

 

 

 

 

CONDENSER COIL & FAN

 

 

 

 

Coil Face Area (Sq Ft)

11.59

 

10.77

12.42

 

 

 

 

 

 

 

 

Fins per In.—Rows—Circuits

25—1—2

 

25—1—2

25—1—2

 

 

 

 

 

 

 

 

Fan Motor—HP (PSC) & RPM

1/12 & 1100

 

1/10 & 1100

1/4 & 1100

 

 

 

 

 

 

 

 

Volts—Hertz—Phase

 

 

208/230—60—1

 

 

 

 

 

 

 

 

Condenser Airflow (CFM)

1800

 

2400

2400

 

 

 

 

 

 

 

 

OPTIONAL EQUIPMENT

 

 

 

 

Support Feet

 

 

KSASF0101AAA

 

 

 

 

 

 

 

 

 

Coastal Filter

 

 

KAACF1001MED

 

Time Delay Relay

 

 

KAATD0101TDR

 

 

 

 

 

 

 

 

 

Cycle Protector

 

 

KSACY0101AAA

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

 

KAACH1201AAA

 

 

 

 

 

 

 

 

Sound Blanket

 

KSASH1801COP

KSASH0601COP

 

 

 

 

 

 

 

 

Start Assist—Capacitor/Relay Type

 

 

KSAHS1501AAA/NA

 

 

 

 

 

 

 

 

 

Start Assist—PTC Type

 

 

KAACS0201PTC/NA

 

 

 

 

 

 

 

 

TXV (Hard Shutoff)

 

KSATX0201HSZ

KSATX0301HSZ

 

 

 

 

 

 

 

 

Piston Body

 

 

KSAPX0101PIS

 

 

 

 

 

 

 

 

 

Filter Drier (Suction Line)

 

 

KH45LG140 (RCD)

 

 

 

 

 

 

 

 

 

Evaporator Freeze Thermostat††

 

 

KAAFT0101AAA

 

 

 

 

 

 

 

 

 

Liquid-Line Solenoid Valve

 

 

KAALS0201LLS

 

 

 

 

 

 

 

 

 

Winter Start Control††

 

 

KAAWS0101AAA

 

 

 

 

 

 

 

 

 

Low-Ambient Pressure Switch

 

 

KSALA0301410

 

 

 

 

 

 

 

 

 

Low-Ambient Controller

 

 

P251-0083 (RCD)

 

 

 

 

 

 

 

 

 

MotorMaster® Control**

 

 

32LT660004 (RCD)

 

 

 

 

 

 

 

 

Ball Bearing Fan Motor

 

HC34GE232(RCD)

HC40GE232(RCD)

 

 

 

 

 

 

 

 

Thermostat—Auto Changeover,

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBNAC01-B

 

Thermostat—Auto Changeover,

 

 

 

 

7-Day Programmable, °F/°C,

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBPAC01-B

 

Thermidistat™ Control—

 

 

 

 

Programmable Thermostat with Humidity Control

 

 

TSTATBBPRH01-B

 

Builder’s Thermostat—Manual Changeover,

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBBAC01-B

 

 

 

 

 

 

 

 

 

Thermostat, Manual Changeover, 5-2 Day

 

 

 

 

Programmable, °F/°C, 1-Stage heat/1-Stage Cool

 

 

TSTATBBSAC01

 

 

 

 

 

 

 

 

 

Outdoor Air Temperature Sensor

 

 

TSTATXXSEN01-B

 

 

 

 

 

 

 

 

 

Backplate for Non-Programmable Thermostat

 

 

TSTATXXNBP01

 

 

 

 

 

 

 

 

 

Backplate for Programmable Thermostat

 

 

TSTATXXPBP01

 

 

 

 

 

 

 

 

 

Backplate for Builder’s Thermostat

 

 

TSTATXXBBP01

 

 

 

 

 

 

 

 

 

Backplate for Standard Programmable

 

 

 

 

Thermostat

 

 

TSTATXXSBP01

 

Thermostat Conversion Kit (4 to 5 wire)—10 Pack

 

 

TSTATXXCNV10

 

 

 

 

 

 

 

 

 

See notes on page 6.