Bryant 533A warranty Unit Size Sound Blanket

Models: 533A

1 24
Download 24 pages 18.21 Kb
Page 7
Image 7

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued

9.Liquid-Line Solenoid Valve (LSV)

An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) and which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.

NOTE: Compressor Start Assist—Capacitor/Relay Type must also be used. Do not use with hard shutoff TXV.

SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. In certain long-line applications. Refer to Residential Split System Long-Line Application Guideline and Service Manual.

10.Low-Ambient Controller

Head pressure controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle the outdoor fan motor in order to maintain condensing temperature within normal operating limits (approximately100°F/37.8°C high and 60°F/15.5°C low). The control will maintain working head pressure at low-ambient temperatures down to 0°F(–17.8°C) when properly installed.

SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).

11.Low-Ambient Pressure Switch

A long life pressure switch which is mounted to outdoor unit service valve. It is designed to cycle the outdoor fan motor in order to maintain head pressure

within normal operating limits (approximately 200 psig to 365 psig). The control will maintain working head pressure at low-ambient temperatures down to 0°F (–17.8°C) when properly installed.

SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).

12.MotorMaster® Control

A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at 100°F ± 10°F (37.8°C ± 5.6°C).

SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C). All commercial installations.

13.Outdoor Air Temperature Sensor

A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat.

SUGGESTED USE: All Bryant programmable thermostats.

14.Piston Body

This piston body is to be used as a replacement for the FK4C Fan Coil R-22 thermostatic expansion valve when used with Puron® (R-410A) air conditioner units. Use piston and piston ring shipped with outdoor unit for installations under 50 ft.

SUGGESTED USE: All Puron® air conditioner installations matched with FK4C Fan Coils.

15.Support Feet

Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base, minimizing corrosion.

SUGGESTED USE: For improved sound ratings. Coastal installations.

Windy areas or where debris is normally circulating. Rooftop installations.

16.Thermostatic Expansion Valve (TXV)

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Hard shutoff valves are available. Do not use with Liquid-Line Solenoid Valve.

NOTE: Compressor Start Assist—Capacitor/Relay Type must also be used. Do not use with Liquid Line Solenoid.

SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. Required for use on all zoning systems.

17.Time-Delay Relay

An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off. SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.

Required for use on all zoning systems.

18.Winter Start Control

An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load conditions.

SUGGESTED USE: All air conditioners where Low-Ambient Controller has been added.

SOUND POWER (dBA)

UNIT

 

 

OCTAVE BAND CENTER FREQUENCY (Hz)

 

 

 

 

 

 

 

 

 

SIZE

125

250

500

1000

2000

4000

8000

024

49.0

58.5

65.0

72.0

66.4

62.0

57.5

030

49.5

62.5

68.5

72.5

67.5

62.5

56.0

 

 

 

 

 

 

 

 

036

57.5

63.5

68.0

75.0

71.0

65.5

58.5

042

54.0

67.5

68.5

72.5

71.5

64.0

60.0

048

57.0

70.5

73.5

75.5

73.0

69.5

64.0

 

 

 

 

 

 

 

 

060

70.5

72.5

72.5

75.0

69.5

65.5

61.5

Not listed in ARI; however, tested in accordance with ARI Standard 270-95.

SOUND POWER (dBA)

UNIT SIZE

W/SOUND BLANKET

W/O SOUND BLANKET

024

74

76

 

 

 

030

75

77

 

 

 

036

76

79

 

 

 

042

77

79

 

 

 

048

78

80

 

 

 

060

78

80

—7—

Page 7
Image 7
Bryant 533A warranty Unit Size Sound Blanket