B. Field Control Wiring

Install a Bryant-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accor- dance with thermostat installation instructions.

Route thermostat cable or equivalent single leads of colored wire from subbase terminals to low-voltage connections on unit (shown in Fig. 9) as described in Steps 1 through 4 below.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

1.If mounted on a roof curb and electrical power is to be run through the basepan, an accessory thru-the- bottom connection kit is required. This is available through the local Bryant distributor. This kit is required to ensure a reliable water-tight connection.

2.If unit is mounted on roof curb and accessory thru- the-bottom service connections are used, route wire through connections.

3.Pass control wires through the hole provided on unit (see connection D in Connection Sizes table in Fig. 7).

4.Feed wire through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 9. The raceway provides the

UL required clearance between the high-voltage and low-voltage wiring.

5.Connect thermostat wires to screw terminals of low- voltage connector (see Fig. 9).

NOTE: If thru-the-bottom power connections are used refer to the accessory installation instructions for information on power wiring. Refer to Fig. 7 for drilling holes in basepan.

C. Heat Anticipator Settings

For units with electric heat, set heat anticipator settings as shown in Table 4.

VI. STEP 6 — ADJUST FACTORY-INSTALLED OPTIONS A. Disconnect Switch

The optional disconnect switch is non-fused. The switch has the capability of being locked in place for safety purposes.

B. Perfect Humidity™ Dehumidification System

Perfect Humidity system operation can be controlled by field installation of a Bryant-approved humidistat (Fig. 11), or light commercial Thermidistat™ device (Fig. 12). To install the humidistat:

1.Route humidistat cable through hole provided in unit corner post.

2.Feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 10. The raceway provides the UL-required clearance between high-voltage and low- voltage wiring.

COOL STAGE 1

Y1/W2

FAN

G

HEAT STAGE 1

W/W1

COOL STAGE 2

Y/Y2

HEAT STAGE 2

O/W2

24 VAC HOT

R

24 VAC COM

C

N/A

 

OUTDOOR AIR

S1

SENSOR

S2

R

G

Y1

Y2

W1

W2

C

IPD/X

WIRE CONNECTIONS TO LOW-VOLTAGE SECTION (CONNECTION BOARD)

CONNECTION

BOARD

FACTORY- INSTALLED DISCONNECT

(OPTION)

RACEWAY

COMPRESSOR

NO. 2

COMPRESSOR

NO. 1

CONVENIENCE OUTLET (OPTION)

THERMOSTAT DIPSWITCH SETTINGS

ON

OFF

A B C D

LEGEND

Field Wiring

NOTE: Underlined letter indicates active thermostat output when configured for A/C operation.

Fig. 9 — Low-Voltage Connections

HOLE IN

END

PANEL

Fig. 10 — Field Control Wiring Raceway

Table 4 — Heat Anticipator Settings

 

 

 

 

 

 

 

 

UNIT VOLTAGE

 

 

 

 

 

 

 

 

 

208/230

 

 

 

 

460

 

 

 

 

575

 

 

UNIT

Heater

 

Configuration

 

Heater

 

 

Configuration

 

Heater

 

 

Configuration

 

 

 

2-Stage

 

 

 

2-Stage

 

 

 

2-Stage

 

kW*

1-Stage

 

kW

1-Stage

 

kW

1-Stage

 

 

 

 

Stage 1

 

Stage 2

 

Stage 1

 

Stage 2

 

Stage 1

 

Stage 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10.4, 16.0

0.3

 

NA

 

NA

13.9, 16.5

0.3

 

 

NA

 

NA

17.0, 34.0

0.3

 

NA

 

NA

551B

24.8, 32.0

0.6

 

0.3

 

0.3

27.8, 33.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42.4, 50.0

0.9

 

0.6

 

0.3

41.7, 50.0

0.6

 

 

0.3

 

0.3

51.0

0.6

 

0.3

 

0.3

*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v or 575 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly.

11

Page 11
Image 11
Bryant 551B Field Control Wiring, Heat Anticipator Settings, VI. Adjust FACTORY-INSTALLED Options A. Disconnect Switch

551B specifications

The Bryant 551B and 551C are two highly efficient air conditioning units designed to provide optimal comfort in residential settings. Known for their reliability and performance, these models are part of Bryant's esteemed line of heating and cooling solutions.

One of the standout features of the Bryant 551B is its two-stage cooling system, which allows for better humidity control and increased comfort. This ensures that homeowners can enjoy consistent temperatures while reducing energy consumption. The unit operates quietly, thanks to its noise-reducing technology, making it an ideal choice for bedrooms and living spaces.

On the other hand, the Bryant 551C builds upon this foundation with its variable-speed compressor. This technology allows the unit to adjust its cooling output according to the specific needs of the home. This results in seamless operation and even greater energy efficiency. Both models also incorporate Bryant's advanced control capabilities, which allow users to monitor and adjust settings remotely via smart devices, adding a layer of convenience and modernity to home climate control.

With an emphasis on durability, both the 551B and 551C feature a galvanized steel cabinet that protects against weather-related damage. The powder coat finish further enhances their resistance to rust and corrosion, ensuring a long lifespan and minimal maintenance.

Another significant characteristic of these units is their excellent Seasonal Energy Efficiency Ratio (SEER) ratings. The 551B boasts a SEER rating of up to 16, while the 551C takes it even further with ratings exceeding 20. This efficiency not only translates to lower energy bills for homeowners but also contributes to a reduced carbon footprint, making these units environmentally friendly options.

Both models are also designed to operate with eco-friendly refrigerants, aligning with modern energy standards and regulations aimed at reducing greenhouse gas emissions.

In summary, the Bryant 551B and 551C are exemplary choices for homeowners looking for reliable, efficient, and high-performing air conditioning solutions. With features such as two-stage and variable-speed compressors, advanced smart technology, and robust construction, these models stand out in the competitive HVAC market. They promise a comfortable indoor environment along with significant energy savings, making them a wise investment for the future.