Table11 – Electrical Data — 569J*12--14D/E 60 Hz Units
WTIHOUTPOWERED CONVENIENCE OUTLET
UNIT V--- P h --- Hz
VOLTAGE
RANGE}COMPRESSOR
1
COMPRESSOR
2OFM(ea) POWER
SUPPLY
MIN MAX RLA LRA RLA LRA WATTS FLA MCA MOCP
569J*12D/E
208/230---3---60 187 253 16 110 16 110 325 1.5 40.6 60
460 ---3--- 60 414 506 7.8 52 7.8 52 325 0.8 22.5 40
575 ---3--- 60 518 633 5.7 39 5.7 39 325 0.6 16.4 30
569J*14D/E
208/230---3---60 187 253 22.4 149 22.4 149 325 1.5 53.4 60
460 ---3--- 60 414 506 10.6 75 10.6 75 325 0.8 25.4 30
575 ---3--- 60 518 633 7.7 54 7.7 54 325 0.6 18.5 25
WTIHPOWERED CONVENIENCE OUTLET
UNIT V--- P h --- Hz
VOLTAGE
RANGE}COMPRESSOR
1
COMPRESSOR
2OFM(ea) POWER
SUPPLY
MIN MAX RLA LRA RLA LRA WATTS FLA MCA MOCP
569J*12D/E
208/230---3---60 187 253 16 110 16 110 325 1.5 43.8 50
460 ---3--- 60 414 506 7.8 52 7.8 52 325 0.8 21.3 25
575 ---3--- 60 518 633 5.7 39 5.7 39 325 0.6 15.7 20
569J*14D/E
208/230---3---60 187 253 22.4 149 22.4 149 325 1.5 58.2 80
460 ---3--- 60 414 506 10.6 75 10.6 75 325 0.8 27.7 35
575 ---3--- 60 518 633 7.7 54 7.7 54 325 0.6 20.2 25
NOTE: See “Legend and Notes for Tables 10 and 11”below

Legendand Notes for Tables 10 and 11

LEGEND:
FL A --- Fu ll Loa d Amp s
LRA --- Locked Rotor Amps
MOCP --- Maximu m Over Current
Protection
NEC --- NationalElectrical Code
RLA --- RatedLoad Amps
}Unitsare su itable for use on electrical systems where voltage
suppliedto the unit terminals isnot below or above the listed
limits.
NOTES:
1. The MCA and Fuse values are calculatedin accordance with
The NEC. Article 440.
2. Motor RLA and LRA values are established in accordance
withUnd erwriters’La boratories (UL). Standard 1995.
3. The 575 --- vu n i t s are UL, Cana d a ---lis t e d onl y.
4. Unbalanced 3-Phase Supply Voltage
Never operate a motorwhere a phase imbalance in supply
voltage is greater than 2%.Use the following formula to de-
terminethe percentage of voltage imbalance.
Example:Sup ply voltage is 230-3-60
%Voltage Imbalance =100 x
maxvoltage deviation from average volt age
averagevoltage
AB= 224 v
BC= 231 v
AC= 226 v
AverageVoltage =
(224+ 231 + 226)
=
681
33
= 227
Determine maximum deviation from average voltag e.
(AB)227 – 224 = 3 v
(BC)231 – 227=4 v
(AC)227 – 226 = 1 v
Maximumd eviation is 4 v.
Determinepercent of voltage imbalance.
%Voltage Imbalance =100 x
4
227
=1.76%
Thisamount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%,conta cty our local electric utility company immediately.
569J