Table 1 — Physical Data — 575B072, 575C090,120 and 541A180 Units

UNIT

575B072

 

575C090

 

 

575C120

 

541A180

NOMINAL CAPACITY (tons)

6

 

7.5

 

 

10

 

15

OPERATING WEIGHTS (lb)

 

 

 

 

 

 

 

 

Aluminum-Fin Coils (standard)

345

 

464

 

 

506

 

803

 

 

 

Copper-Fin Coils (optional)

N/A

 

565

 

 

607

 

945

REFRIGERANT*

 

 

 

 

 

R-22

 

 

Operating Charge, Typical (lb)†

20

 

20

 

 

22

 

37

 

 

 

Shipping Charge (lb)

1

 

9

 

 

9

 

3

COMPRESSOR

 

 

Scroll

 

 

 

 

Semi-hermetic reciprocating

Qty...Model

1...SR_75

 

1...ZR_94

 

 

1...ZR125

 

1...06DF537††

 

 

Oil Charge (oz)

88

 

90

 

 

110

 

128

No. Cylinders

 

 

N/A

 

 

 

 

6

Speed (rpm)

 

3500

 

 

 

 

1750

OUTDOOR FANS

 

 

 

 

 

 

 

 

Qty...Rpm

1…1100

 

 

2…1100

 

2…1075

 

 

 

Diameter (in.)

26

 

 

22

 

26

Nominal Hp

3/4

 

 

1/4

 

1/2

Nominal Airflow (cfm total)

6300

 

 

6500

 

11,000

Watts (total)

750

 

 

570

 

1460

OUTDOOR COILS (Qty)

1

 

 

2

 

1

Face Area (sq ft total)

24

 

 

29.2

 

29.2

Rows...Fins/in.

2…18

 

 

2…17

 

3…15

Storage Capacity (lb)**

17.3

 

 

34.2

 

40.1

CONTROLS

 

 

 

 

 

 

 

 

Pressurestat Settings (psig)

 

 

 

 

 

 

 

 

High Pressure

 

 

 

 

 

 

 

 

Open

420

 

 

428 ± 10

 

395 ± 20

 

 

 

Close

300

 

 

320 ± 20

 

295 ± 20

Low Pressure

 

 

 

 

 

 

 

 

Open

5

 

 

7 ± 3

 

7 ± 3

Close

20

 

 

22 ± 5

 

22 ± 5

PIPING CONNECTIONS (in. ODM)

 

 

 

 

 

 

 

 

Vapor

11/8

 

11/8

 

 

13/8

 

15/8

 

 

 

Liquid

5/8

 

1/2

 

 

1/2

 

5/8

*Unit is factory supplied with holding charge only.

†Typical operating charge with 25 ft of interconnecting pipe. **Storage capacity of condenser coil with 80% full of liquid at 95 F.

††Equipped with an electric solenoid unloader, capacity steps are 100% and 67%.