IV. COMPLETE ELECTRICAL CONNECTIONS

A. Power Supply

Electrical characteristics of available power supply must agree with nameplate rating. Supply voltage must be within tolerances shown in Table 7. Phase imbalance must not exceed 2%. Operation of unit on improper supply voltage or with excessive phase imbalance constitutes abuse and is not covered by Bryant warranty.

Per local code requirements, provide an adequate fused disconnect switch within sight of unit and out of reach of children. Provision the switch for locking open (off) to prevent power from being turned on while unit is being serviced. The disconnect switch, fuses, and field wiring must comply with local requirements. Refer to Table 7 for unit electrical data.

B. Power Wiring

All power wiring must comply with applicable local require- ments. Run power wires from disconnect switch through unit power opening and connect to terminal block inside the unit control box. Unit must be grounded.

C. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance:

% Voltage Imbalance:

=100 x max voltage deviation from average voltage average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

452 + 464 + 455

Average Voltage =

3

= 1371 3

= 457

(AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v

(AC) 457 – 455 = 2 v Maximum deviation is 7 v.

Determine percent of voltage imbalance. % Voltage Imbalance= 100 x 4577

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

WARNING: Unit cabinet must have an uninter- rupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (American National Standards Institute/National Fire Protection Association), and local electrical codes. Failure to follow this warning could result in the installer being liable for personal injury of others.

IMPORTANT: Operation of unit on improper power supply voltage or with excessive phase imbalance constitutes abuse and is not covered by Bryant warranty.

D. General Wiring Notes (See Fig. 8-13)

1.A crankcase heater is wired in the control circuit so it is always operable as long as power supply disconnect is on, even if any safety device is open or unit stop/ start switch is off.

2.The power-circuit field supply disconnect should never be open except when unit is being serviced or is to be down for a prolonged period. When operation is resumed, crankcase heater should be energized for 24 hours before start-up. If system is to be shut down for a prolonged period, it is recommended that the suction and discharge valves be closed to prevent an excessive accumulation of refrigerant in the com- pressor oil.

3.Terminals for field power supply are suitable for cop- per, copper-clad aluminum, or aluminum conductors.

4.Bryant recommends an indoor airflow switch (field supplied) be installed and interlocked with the outdoor unit. This prevents the outdoor unit from operating if indoor airflow fails (broken fan belt, etc.). Operation of the compressor in vacuum can damage bearing surfaces. Install indoor airflow switch in a convenient location at the indoor supply air duct and wire per Fig. 14.

5.If the system is equipped with an accessory electric heater, refer to the 524A-H installation instructions and tables.

E.Control Circuit Wiring

Control voltage is 24 v. See unit label diagram for field supplied wiring details. Route control wires through opening in unit to connection in unit control box.

Control Transformer Wiring

On 208/230V units, check the transformer primary wiring connections. See Fig. 8 or refer to unit label diagram.

For 575B,C Unit — If unit will be operating at 208-3-60 power, remove black wire (BLK) from the transformer pri- mary connection labeled “230” and move it to the connection labeled “208”. See Fig. 8.

For 541A Unit — Transformers no. 1 and 2 are wired for a 230-v unit. If a 208/230-v unit is to be run with a 208-v power supply, the transformers must be rewired as follows:

1.Remove cap from red (208 v) wire.

2.Remove cap from orange (230 v) spliced wire.

3.Replace orange wire with red wire.

4.Recap both wires.

IMPORTANT: BE CERTAIN UNUSED WIRES ARE CAPPED. Failure to do so may result in damage to the transformer.

9

Page 9
Image 9
Bryant 575C, 575B, 541A dimensions IV. Complete Electrical Connections

541A, 575B, 575C specifications

The Bryant 575B, 541A, and 575C heating and cooling units are part of the renowned Bryant lineup, designed to provide efficient and reliable climate control solutions for residential and commercial spaces. These models are particularly celebrated for their impressive performance, innovative technologies, and user-friendly operations.

Starting with the Bryant 575B, this model is a high-efficiency air conditioner that boasts a SEER rating of up to 20.5. It utilizes a variable-speed compressor that adjusts its output based on the temperature needs of the home, leading to enhanced energy savings and consistent indoor comfort. The 575B is equipped with a steel cabinet that resists corrosion and damage while also minimizing noise levels during operation. Additionally, its environmentally friendly R-410A refrigerant helps to reduce the system's ecological footprint.

Moving on to the Bryant 541A, this unit is a formidable gas furnace known for its exceptional heating capabilities. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 97.5%, the 541A efficiently transforms fuel into heat, ensuring lower energy bills during cold months. It incorporates advanced technologies such as a two-stage gas valve and a variable-speed blower motor, allowing it to respond dynamically to the heating demands of the home. The insulated cabinet construction further enhances energy efficiency by preventing heat loss and increasing comfort.

Lastly, the Bryant 575C model is a versatile heat pump that offers both heating and cooling functionalities, ideal for regions with moderate heating and cooling needs. It features a SEER rating of up to 20 and an HSPF (Heating Season Performance Factor) rating of up to 10.5, making it an energy-efficient choice year-round. The 575C comes with a streamlined design that integrates a variable-speed compressor, which helps maintain precise temperatures and minimizes energy consumption. Additionally, its quiet operation is enhanced by sound insulation, providing a serene indoor environment.

All three models are designed with durability in mind, featuring robust construction materials that withstand the elements. They can be easily integrated with smart thermostats, providing homeowners with greater control over their energy use. With exceptional efficiency ratings, durable designs, and advanced features, the Bryant 575B, 541A, and 575C represent a perfect blend of comfort and cutting-edge technology. Whether for heating or cooling, these units deliver outstanding performance to meet the needs of today's energy-conscious consumers.