III. COMPLETE REFRIGERANT PIPING CONNECTIONS
Refrigerant lines must be carefully designed and constructed to ensure equipment reliability and efficiency. Line length, pressure drop, compressor oil return, and vertical separation are several of the design criteria that must be evaluated. See Table 2.
IMPORTANT: Do not bury refrigerant piping underground.
IMPORTANT: Piping must be properly sized and installed for the system to operate efficiently.
A. Check Vertical Separation
If there is any vertical separation between the indoor and out- door units, check to ensure that the separation is within allowable limits. Relocate equipment if necessary. See Table 3.
B. Refrigerant Line Sizing
Consider the length of the piping required between the out- door and indoor units. The maximum allowable line length is 100 ft. See Table 3. Refrigerant suction piping should be insulated.
IMPORTANT: A refrigerant receiver is not provided with the unit. Do not install a receiver.
IMPORTANT: For 575C090,120 applications with liquid lift greater than 20 ft, use
Table 2 — Refrigerant Piping Sizes
|
|
| LENGTH OF PIPING ft |
| MAXIMUM | |||||
OUTDOOR |
|
|
| LIQUID | ||||||
UNIT |
|
|
| Line Size (in. OD) |
|
| LINE | |||
|
|
|
|
|
|
|
|
|
| (in. OD)* |
| L |
| V |
| L | V |
| L | V | |
|
|
|
|
| ||||||
575B072 | 1/2 |
| 11/8 |
| 5/8 | 11/8 |
| 5/8 | 11/8 | 5/8 |
575C090 | 3/8 |
| 11/8 |
| 1/2 | 11/8 |
| 1/2 | 11/8 | 5/8 |
575C120 | 1/2 |
| 13/8 |
| 1/2 | 13/8 |
| 1/2 | 13/8 | 5/8 |
541A180 | 5/8 |
| 15/8 |
| 3/4 | 15/8 |
| 3/4 | 15/8 | 3/4 |
*If there is a vertical separation between indoor and outdoor units, see Table 3 — Maximum Vertical Separation.
LEGEND
L — Liquid Line | V — Vapor Line |
NOTES:
1.Pipe sizes are based on a 2 F loss for liquid and vapor lines.
2.Pipe sizes are based on the maximum linear length, shown for each column, plus a 50% allowance for fittings.
3.Charge units with
4.Maximum line length must not exceed 100 ft.
5.Do not bury refrigerant piping.
Table 3 — Maximum Vertical Separation*
OUTDOOR | INDOOR UNIT |
| DISTANCE FT | ||
| Outdoor Unit | ||||
UNIT |
| ||||
| Above | ||||
|
|
|
|
| |
575B |
| 072 | 090 |
| 50 |
575C |
| 090 | 090 |
| 60 |
| 120 | 120 |
| 60 | |
|
|
| |||
541A |
| 180 | 180 |
| 80 |
*Vertical distance between indoor and outdoor units.
C. Install Filter Drier(s) and Moisture Indicator(s)
Every unit should have a filter drier and
Select the filter drier for maximum unit capacity and minimum pressure drop. Complete the refrigerant piping from indoor
unit to outdoor unit before opening the liquid and vapor lines at the outdoor unit. For specific filter driers see Table 4.
D. Liquid Line Piping Procedure
Pipe the system liquid line as follows:
WARNING: Unit is pressurized with a holding charge of refrigerant. Recover
1.Open service valves in sequence:
a.Discharge service valve on compressor.
b.Suction service valve on compressor.
c.Liquid line valve.
2.Remove
3.Attach refrigerant recovery device and recover hold- ing charge.
4.Remove runaround loop (581A180 only).
5.Connect system liquid line from liquid connection of outdoor unit (575B,C, 541A) to indoor unit
E.Liquid Line Solenoid Valve
Addition of a liquid solenoid valve (LLSV) is required (except for 541A180 units that already have LLSV
The LLSV must be installed at the outdoor unit with the flow arrow pointed toward the outdoor unit
LEGEND
TXV — Thermostatic Expansion Valve