Table 4 — Refrigerant Specialties Part Numbers
UNIT | LIQUID LINE | LIQUID LINE | LLSV COIL | SIGHT GLASS | FILTER DRIER | |
SIZE | SOLENOID VALVE (LLSV) | |||||
|
|
|
| |||
575B072 | 1/2″ | 200RB | AMI1TT4 | * | ||
5/8″ | 200RB | AMI1TT5 | * | |||
| ||||||
575C090 | 3/8″ | 200RB | AMI1TT3 | |||
1/2″ | 200RB | AMI1TT4 | ||||
| ||||||
575C120 | 1/2″ | 200RB | AMI1TT4 | |||
541A180 | 5/8″ | ** | ** | AMI1TT5 | ||
3/4″ | ** | ** | AMI1TT5 | |||
|
*A filter drier is shipped loose with the 575B072 units. †Bushings required.
**Factory Installed.
F. Provide Safety Relief
A fusible plug is located on the compressor crankcase or in the liquid line. See Fig. 6. Do not cap this plug. If local code requires additional safety devices, install them as directed.
Head Pressure Control (541A180 only)
Fan cycling for head pressure control is a standard offering but is functional on the cooling cycle only. Number 2 fan cycles as a function of liquid pressure. Fan cycling pressure switch cycles the fan off at 160 ± 10 psig as pressure decreases and cycles back on at 255 ± 10 psig. Switch is auto- matically bypassed in heating cycle. Table 5 shows minimum outdoor air temperature for full cooling capacity.
G. Vapor Line Piping Procedure
Connect system vapor line to the vapor line stub on the out- door unit and the vapor stubs on the indoor unit. At the indoor unit, construct vapor piping branches as shown in Fig. 7 for good mixing of the refrigerant leaving the indoor coil during cooling. This will ensure proper TXV (thermo- static expansion valve) bulb sensing.
Where vapor line is exposed to outdoor air, line must be insu- lated. See Table 6 for insulation requirements.
Table 5 — Minimum Outdoor Air
Operating Temperature
|
|
| % | MINIMUM OUTDOOR TEMP — F* | |
UNIT |
| COMPRESSOR | Standard | Head Pressure | |
|
|
| CAPACITY | Unit | Control† |
575B |
| 072 |
| 0 | 0 |
575C |
| 090 | 100 | 35 | |
| 120 |
| 35 | ||
|
|
| |||
541A |
| 180 | 100 | 23 | |
| 67 | 36 | |||
|
|
|
*Applies to Cooling mode of operation only.
†Wind baffles
Table 6 — Insulation for Vapor Line Exposed
to Outdoor Conditions
LENGTH OF EXPOSED | INSULATION THICKNESS† | |
VAPOR LINE* | ||
| ||
ft | in. | |
10 | 3/8 | |
25 | 1/2 | |
35 | 3/4 | |
50 | 3/4 |
Fig. 6 — Location of Fusible Plug —
541A180 Unit
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 7 — Vapor Line Branch Piping Details
*Recommended vapor line insulation for piping exposed to outdoor conditions to prevent loss of heating during heating cycle. When vapor line goes through interior spaces, insulation should be selected to pre- vent condensation on cooling cycle. Heating capacity should be reduced 1000 Btuh if over 35 ft of vapor line with 3/4 in. insulation is exposed to outdoor conditions.
†Closed cell foam insulation with a thermal conductivity of: 0.28 Btu
• in./ft2 • h • °F.