581J

Table 3 – RTU Open Controller Inputs and Outputs

 

 

POINT NAME

BACnet OBJECT

 

TYPE OF I/O

CONNECTION PIN

 

 

NAME

 

NUMBER(S)

 

 

 

 

 

 

 

 

DEDICATED INPUTS

 

Space Temp / Zone Temp

zone_temp

 

AI (10K Thermistor)

J20--- 1, 2

Supply Air Temperature

sa_temp

 

AI (10K Thermistor)

J2--- 1, 2

Outdoor Air Temperature

oa_temp

 

AI (10K Thermistor)

J2--- 3, 4

Space Temperature Offset Pot

stpt_adj_offset

 

AI (100K Potentiometer)

J20--- 3

Safety Chain Feedback

safety_status

 

DI (24 VAC)

J1--- 9

Compressor Safety Status

comp_status

 

DI (24 VAC)

J1--- 2

Fire Shutdown Status

firedown_status

 

DI (24 VAC)

J1--- 10

Enthalpy Status

enthalpy_status

 

DI (24 VAC)

J2--- 6

Humidistat Input Status

humstat_status

 

DI (24 VAC)

J5--- 7

 

 

 

CONFIGURABLE INPUTS

 

Indoor Air CO2

iaq

 

AI (4--- 20 ma)

 

Outdoor Air CO2

oaq

 

AI (4--- 20 ma)

J4--- 2 or J4--- 5

Space Relative Humidity

space_rh

 

AI (4--- 20 ma)

 

Supply Fan Status*

sfan_status

 

DI (24 VAC)

 

Filter Status*

filter_status

 

DI (24 VAC)

J5--- 1 or J5---3 or

Door Contact Input*

door_contact_status

 

DI (24 VAC)

J5 5 or J5--- 7

Occupancy Contact*

occ_contact_status

 

DI (24 VAC)

 

 

 

 

OUTPUTS

 

 

Economizer Output

econ_output

 

AO (4--- 20ma)

J2--- 5

Supply Fan Relay State

sfan

 

DO Relay (24VAC , 1A)

J1--- 4

Compressor 1 Relay State

comp_1

 

DO Relay (24VAC , 1A)

J1--- 8

Compressor 2 Relay State

comp_2

 

DO Relay (24VAC , 1A)

J1--- 7

Heat Stage 1 Relay State

heat_1

 

DO Relay (24VAC , 1A)

J1--- 6

Heat Stage 2 Relay State

heat_2

 

DO Relay (24VAC , 1A)

J1--- 5

Power Exhaust Relay State

pexh

 

DO Relay (24VAC , 1A)

J11--- 3

Dehumidification Relay State

dehum

 

DO Relay (24VAC, 1A)

J11--- 7, 8

LEGEND

 

 

 

 

AI

---

Analog Input

 

 

 

 

AO ---

Analog Output

 

 

 

 

DI

---

Discrete Input

 

 

 

 

DO ---

Discrete Output

 

 

 

 

*These inputs (if installed) take the place of the default input on the specific channel according to schematic. Parallel pins J5--- 1 = J2--- 6, J5--- 3 = J1--- 10, J5---5 = J1--- 2 are used for field--- installation.

The RTU Open controller requires the use of a Bryant space sensor. A standard thermostat cannot be used with the RTU Open system.

Supply Air Temperature (SAT) Sensor —

On FIOP-equipped 581J unit, the unit is supplied with a supply-air temperature (SAT) sensor (33ZCSENSAT). This sensor is a tubular probe type, approx 6-inches (12.7 mm) in length. It is a nominal 10-k ohm thermistor.

The SAT is factory-wired. The SAT probe is wire-tied to the supply-air opening (on the horizontal opening end) in its shipping position. Remove the sensor for installation. Re-position the sensor in the flange of the supply-air opening or in the supply air duct (as required by local codes). Drill or punch a 1/2-in. hole in the flange or duct.

SUPPLY AIR TEMPERATURE

SENSOR

SUPPLY AIR

ROOF CURB

RETURN AIR

C08200

Use two field-supplied, self-drilling screws to secure the sensor probe in a horizontal orientation. See Fig. 37.

Fig. 37 - Typical Mounting Location for Supply Air Temperature (SAT) Sensor on Small Rooftop Units

Outdoor Air Temperature (OAT) Sensor —

The OAT is factory-mounted in the EconoMi$er2 (FIOP or accessory). It is a nominal 10k ohm thermistor attached to an eyelet mounting ring.

26

Page 26
Image 26
Bryant 581J installation instructions RTU Open Controller Inputs and Outputs, Supply Air Temperature SAT Sensor

581J specifications

The Bryant 581J is a high-efficiency gas furnace that exemplifies advanced heating technology and innovative design. Known for its reliability and comfort, the Bryant 581J offers impressive performance features that cater to both residential and commercial heating needs. One of its standout characteristics is the two-stage heating system, which allows the furnace to operate at a lower stage when the heating demand is modest, providing improved comfort and energy efficiency. This feature also minimizes temperature fluctuations, ensuring a more consistent and comfortable indoor environment.

Energy efficiency is a critical aspect of the Bryant 581J. With an annual fuel utilization efficiency (AFUE) rating of up to 96%, this furnace is designed to convert a high percentage of fuel into usable heat, which helps homeowners save on energy bills. The high-efficiency design also contributes to a reduced carbon footprint, aligning with modern environmental concerns.

The Bryant 581J is equipped with technologically advanced features, including the ComfortTechâ„¢ control system. This system enables enhanced temperature regulation and integrates easily with smart home systems, allowing homeowners the convenience of remote control through smartphones and tablets. Additionally, the furnace includes an electronically commutated motor (ECM) blower, which optimizes airflow and reduces energy consumption while enhancing the overall comfort level within the space.

Noise reduction is another key characteristic of the Bryant 581J. The furnace is engineered with sound-dampening technology, resulting in quieter operation compared to conventional furnaces. This attention to noise management makes it an appealing choice for residential applications, where peace and tranquility are crucial.

The durable construction of the Bryant 581J ensures longevity and reliability. With a robust cabinet and quality materials, it is built to withstand the rigors of daily operation. Furthermore, the furnace comes with a warranty that provides peace of mind, protecting the investment over the years.

Overall, the Bryant 581J represents a blend of efficiency, advanced technology, and reliable performance. With its high AFUE rating, innovative features, and quiet operation, it stands out in the market as a top choice for anyone seeking a dependable heating solution. Whether for new installations or replacements, the Bryant 581J is designed to meet the heating demands of today's energy-conscious homeowners.