Bryant 581J Fire Or Explosion Hazard, Condensate Drain Pan Side View, Orifice Hole

Models: 581J

1 40
Download 40 pages 41.76 Kb
Page 16
Image 16
FIRE OR EXPLOSION HAZARD

NOTE: Pressure test the gas supply system after the gas supply piping is connected to the gas valve. The supply piping must be disconnected from the gas valve during the testing of the piping systems when test pressure is in excess of 0.5 psig (3450 Pa). Pressure test the gas supply piping system at pressures equal to or less than 0.5 psig (3450 Pa). The unit heating section must be isolated from the gas piping system by closing the external main manual shutoff valve and slightly opening the ground-joint union.

Check for gas leaks at the field-installed and factory-installed gas lines after all piping connections have been completed. Use soap-and-water solution (or method specified by local codes and/or regulations).

 

 

!

WARNING

 

 

581J

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal

 

 

 

 

injury, death and/or property damage.

SConnect gas pipe to unit using a backup wrench to

avoid damaging gas controls.

SNever purge a gas line into a combustion chamber. S Never test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for the detection of leaks to check all connections.

S Use proper length of pipe to avoid stress on gas control manifold.

NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never redrill an orifice. A burr-free and squarely aligned orifice hole is essential for proper flame characteristics.

Step 11 — Install External Condensate Trap and Line

The unit has one 3/4-in. condensate drain connection on the end of the condensate pan and an alternate connection on the bottom. See Fig. 22. Unit airflow configuration does not determine which drain connection to use. Either drain connection can be used with vertical or horizontal applications.

When using the standard side drain connection, ensure the red plug in the alternate bottom connection is tight. Do this before setting the unit in place. The red drain pan can be tightened with a 1/2-in. square socket drive extension.

To use the alternate bottom drain connection, remove the red drain plug from the bottom connection (use a 1/2-in. square socket drive extension) and install it in the side drain connection.

CONDENSATE PAN (SIDE VIEW)

 

ALTERNATE

STANDARD

DRAIN PLUG

BOTTOM DRAIN

SIDE DRAIN

(FACTORY-INSTALLED)

 

 

C08021

Fig. 22 - Condensate Drain Pan (Side View)

The piping for the condensate drain and external trap can be completed after the unit is in place. See Fig. 23.

BURNER Fig. 22 - Condensate Drain Pan (Side View)

MINIMUM PITCH

1” (25mm) PER

10’ (3m) OF LINE

TO ROOF

DRAIN

BASE RAIL

2˝ (51) MIN

OPEN

VENT Fig. 21 - Orifice Hole

SEE NOTE

Fig. 23 - Condensate Drain Piping Details ROOF

CURB

DRAIN PLUG

ORIFICE

A93059

Fig. 21 - Orifice Hole

NOTE: Trap should be deep enough to offset maximum unit static difference. A 4” (102) trap is recommended.

C08022

Fig. 23 - Condensate Drain Piping Details

All units must have an external trap for condensate drainage. Install a trap at least 4-in. (102 mm) deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do not use a pipe size smaller than the unit connection (3/4-in.).

16

Page 16
Image 16
Bryant 581J Fire Or Explosion Hazard, Condensate Drain Pan Side View, Orifice Hole, Condensate Drain Piping Details