581J
Provide a
All units except
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Table 5. On
NOTE: Check all factory and field electrical connections for tightness.
Convenience Outlets —
!WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it.
| |
Convenience | Transformer |
Outlet |
|
GFCI |
|
Fuse
Switch
Control Box
Access Panel
C08128
Fig. 26 - Convenience Outlet Location
Two types of convenience outlets are offered on 581J models:
provide a
Installing Weatherproof Cover: A weatherproof
The weatherproof cover kit is shipped in the unit’s control box. The kit includes the hinged cover, a backing plate and gasket.
DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET.
Remove the blank cover plate at the convenience outlet; discard the blank cover.
Loosen the two screws at the GFCI duplex outlet, until approximately
Mount the weatherproof cover to the backing plate as shown in Fig. 27. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching.
COVER – | RECEPTACLE | |||||
WEATHERPROOF | ||||||
NOT INCLUDED | ||||||
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
|
BASE PLATE FOR
GFCI RECEPTACLE
C09022
Fig. 27 - Weatherproof Cover Installation
18