Bryant 581J Outdoor Air Enthalpy Control PNO 33CSENTHSW, LEDs, Differential Enthalpy Control

Models: 581J

1 40
Download 40 pages 41.76 Kb
Page 33
Image 33
Table 4 – LEDs

 

 

Table 4 – LEDs

 

The LEDs on the RTU Open show the status of certain functions

 

 

 

If this LED is on...

 

Status is...

 

 

 

Power

 

RTU Open has power

 

 

 

Rx

 

RTU Open is receiving data from the network segment

 

 

 

Tx

 

RTU Open is transmitting data over the network segment

 

 

 

DO#

 

The digital output is active

 

The Run and Error LEDs indicate control module and network status

If Run LED shows...

And Error LED shows...

2 flashes per second

Off

 

 

2 flashes per second

2 flashes,

alternating with Run LED

 

2 flashes per second

3 flashes,

then off

 

2 flashes per second

4 flashes,

then pause

 

 

 

2 flashes per second

On

 

 

5 flashes per second

On

 

 

5 flashes per second

Off

 

 

7 flashes per second

7 flashes per second, alternating with

Run LED

 

 

 

14 flashes per second

14 flashes per second,

alternating with Run LED

 

On

On

 

 

Status is...

Normal

Five minute auto---restart delay after system error

Control module has just been formatted

Two or more devices on this network have the same ARC156 network address

Exec halted after frequent system errors or control programs halted

Exec start---up aborted, Boot is running Firmware transfer in progress, Boot is running

Ten second recovery period after brownout

Brownout

Failure. Try the following solutions:

STurn RTU Open off, then on. S Format RTU Open.

S Download memory to RTU Open. S Replace RTU Open.

581J

NOTE: Refer to Catalog No. TS-5580J-01 for complete configuration of RTU Open operating sequences. Contact your Bryant applications engineer for details on configuration and troubleshooting of connected networks.

Outdoor Air Enthalpy Control (PNO 33CSENTHSW)

Enthalpy

 

Switch

 

24V

RED

GND

BLK

LOW

GRA

PL6-1 (24-V)

PL6-4 (COM)

7CTB ECON

(RTU Open: to J2-6)

The enthalpy control (33CSENTHSW) is available as a field-installed accessory to be used with the EconoMi$er2 damper system. The outdoor air enthalpy sensor is part of the enthalpy control. (The separate field-installed accessory return air enthalpy sensor (33CSENTSEN) is required for differential enthalpy control. See Fig. 53.)

Locate the enthalpy control in the economizer next to the Actuator Motor. Locate two GRA leads in the factory harness and connect the gray lead labeled “ESL” to the terminal labeled “LOW”. See Fig. 53. Connect the enthalpy control power input terminals to economizer actuator power leads RED (connect to 24V) and BLK (connect to GND).

Factory Wiring Harness

C11169

Fig. 53 - Enthalpy Switch (33CSENTHSW) Connections

The outdoor enthalpy changeover setpoint is set at the enthalpy controller.

Differential Enthalpy Control —

Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions. Install the outdoor air enthalpy control as described above. Add and install a return air enthalpy sensor.

33

Page 33
Image 33
Bryant 581J Outdoor Air Enthalpy Control PNO 33CSENTHSW, LEDs, Enthalpy Switch 33CSENTHSW Connections