Fig. 62 - EconoMi$ert IV Wiring

581J

Economizer

2 Position Damper

Unit Without Economizer or

2 Position Damper

 

 

 

 

C10150

Fig. 62 - EconoMi$ert IV Wiring

Step 13 — Adjust Factory-Installed Options

Smoke Detectors —

Smoke detector(s) will be connected at the Controls Connections Board, at terminals marked “Smoke Shutdown”. Remove jumper JMP 3 when ready to energize unit.

EconoMi$er IV Occupancy Switch —

Refer to Fig. 62 for general EconoMi$er IV wiring. External occupancy control is managed through a connection on the Central Terminal Board.

If external occupancy control is desired, connect a time clock or remotely controlled switch (closed for Occupied, open for Unoccupied sequence) at terminals marked OCCUPANCY on CTB. Remove or cut jumper JMP 2 to complete the installation.

Step 14 — Install Accessories

High Altitude Gas kits Flue Discharge Deflector Flue Exhaust Heat Shield Low Ambient Controls Thermostat / Sensors

Two-Position motorized outside air damper

EconoMi$er2 (without control/for external signal and integrated barometric relief)

EconoMi$er2 (without control/for external signal) Power Exhaust

Differential dry-bulb sensor (EconoMi$er IV) Outdoor enthalpy sensor

Differential enthalpy sensor CO2 sensor

Louvered hail guard Phase monitor control Winter Start kit

Available accessories include: Roof Curb

Thru-base connection kit (must be installed before unit is set on curb)

LP conversion kit

Manual outside air damper

Refer to separate installation instructions for information on installing these accessories.

Pre-Start and Start-Up

This completes the mechanical installation of the unit. Refer to the unit’s Service Manual for detailed Pre-Start and Start-up instructions.

Copyright 2011 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 04/11

Catalog No: II581J---10

 

 

 

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

 

Replaces: II581J--- 01 & II581J--- 03

40

Page 40
Image 40
Bryant 581J Adjust Factory-InstalledOptions, Install Accessories, EconoMi$ert IV Wiring, Smoke Detectors