607C-- -- A
VERTICAL ECONOMIZER
(FACTORY INSTALLED OPTION)
GENERAL
Economizers are recommended for only commercial packaged products that have X13 motors. The Economizer system utilizes the latest technology available for integrating the use of free cooling with mechanical cooling for rooftop units. The solid state control system optimizes energy consumption, zone comfort, and equipment cycling by operating the compressors when the outdoor air temperature is too warm, integrating the compressor with outdoor air when free cooling is available, and locking out the compressor when outdoor air temperature is too cold. Demand ventilation is supported.
The Economizer system utilizes
Barometric relief dampers provide natural building pressurization control. Barometric relief dampers are built into the design and are standard. See Table for Hood Package contents. See Table 11 for sensor usage.
Table 10 – Package Contents
| SMALL CHASSIS |
| LARGE CHASSIS |
| (Sizes 30) | (Sizes 36, 42, 48, and 60) | |
|
|
|
|
Qty | Content Description | Qty | Content Description |
|
|
|
|
1 | Hood Side, Right | 1 | Hood Side, Right |
|
|
|
|
1 | Hood Side, Left | 1 | Hood Side, Left |
|
|
|
|
2 | Angle, Filter | 2 | Angle, Filter |
|
|
|
|
1 | Aluminum Filter | 1 | Aluminum Filter |
| (521 x 419 x 25 mm) |
| (521 x 419 x 25 mm) |
|
|
|
|
18 | Screws | 18 | Screws |
(#10 | (#10 | ||
| Washer) |
| Washer) |
|
|
|
|
2 | Screws | 2 | Screws |
(#8 | (#8 | ||
| Head) |
| Head) |
|
|
|
|
|
| 1 | Bracket, Sensor |
|
|
|
|
Table 11 – Economizer Sensor Usage
| ECONOMIZER WITH OUTDOOR AIR DRY BULB | |||
APPLICATION |
| SENSOR | ||
|
|
|
| |
| Accessories Required | |||
|
|
|
| |
Outdoor Air Dry Bulb | None, The outdoor air dry bulb sensor is factory | |||
| installed. | |||
|
| |||
|
|
|
| |
Single Enthalpy | HH57AC078 | |||
|
|
|
| |
Differential Enthalpy | HH57AC078 and CRENTDIF004A00* | |||
|
|
|
|
|
CO2 for DCV Control |
|
|
|
|
Using a | 33ZCSENC02 or CGCDXSEN004A00 | |||
CO2 Sensor |
|
|
|
|
CO2 for DCV Control | 33ZCSENC02 or |
|
|
|
CGCDXSEN004A00{ |
| or | CRCBDIOX005A00{ { | |
Using a | and 33ZCASPCO2 or |
| ||
Mounted CO2 Sensor |
|
|
| |
CGCDXASP00100** |
|
|
|
*CRENTDIF004A00 accessory is used on many different base units. As such, these kits may contain parts that will not be needed for installation.
{33ZCSENCO2 and CGCDXSEN004A00 are accessory CO2 sensors. **33ZCASPC02 AND CGCDXASP00100 are accessory aspirator boxes required for
{{CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 AND 33ZVASPC02 accessories.
ACCESSORIES
The economizer has several
Table 12 – Accessory List
DESCRIPTION | PART NUMBER |
|
|
Outdoor Air Enthalpy Sensor | HH57AC078 |
|
|
Indoor Air Enthalpy Sensor | CRENTDIF004A00 |
|
|
Return Air CO2 Sensor | CRCBDIOX005A00 |
CO2 Room Sensor | 33ZCSENX02 Or |
CGCDXSEN004A00 | |
|
|
Aspirator Box for duct Mount CO2 Sensor | 33ZCASPC02 Or |
CGCDXASP001A00 | |
Space Temperature and CO2 Room | 33ZCT55C02 |
Sensor with Override |
|
Space Temperature and CO2 Room | 33ZCT56C02 |
Sensor with Override and Set Point | |
| |
|
|
Heat Pump Relay Package | CPRLYKIT001A00 |
|
|
INSTALLATION
Small Chassis
To install the Vertical Economizer on the small chassis perform the following procedure:
1. Turn off unit power supply and install lockout tag.
!WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to system and install lockout tag. There may be more than one disconnect switch. Turn off accessory heater power switch if applicable.
2.Remove economizer hood top panel from the return side of the unit. See Fig. 23. Keep screws and panel next to the unit.
3.Open economizer hood package found on the top skid.
4.Remove red shipping tape that attaches the outside air temperature (OAT) sensor to the economizer assembly. Using two #8 fasteners, found in the hood package, attach the OAT sensor to the economizer according to Fig. 24.
NOTE: See label attached to economizer for OAT installing details.
5.Remove horizontal return duct cover panel and cut the wire ties that hold the hood divider to the economizer assembly. Slide hood divider off from the two slots holding it in place and place next to the unit. See Fig. 25.