12
CONTROL
CURVE
A
B
C
D
18 16 14
CONTROL POINT |
|
|
|
|
|
|
|
|
| ||||
APPROX ˚F (˚C) |
|
|
|
|
|
|
|
|
|
| |||
AT 50% RH |
|
|
|
|
|
|
|
|
|
|
| ||
73 (23) |
|
|
|
|
|
|
|
|
|
|
| ||
70 (21) |
|
|
|
|
|
|
|
|
|
|
| ||
67 (19) |
|
|
|
|
|
|
|
|
|
|
| ||
63 (17) |
|
|
|
|
|
|
|
| DRY | ||||
|
|
|
|
|
|
| POUND | ||||||
|
|
|
|
|
|
| 34 |
| |||||
|
|
|
|
|
| PER |
|
|
| ||||
|
|
|
|
|
| 32 |
|
|
|
|
| ||
|
|
|
| BTU |
|
|
|
|
|
|
| ||
|
|
| – | 30 |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
| 28 |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||
26 |
|
|
|
|
|
|
|
|
|
|
| ||
| ENTHALPY |
|
|
|
|
|
|
|
|
|
|
| |
24 |
|
|
|
|
|
|
|
|
|
|
|
| |
22 |
|
|
|
|
|
|
|
|
|
|
|
| |
20 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 55 |
| |
|
|
|
|
|
|
|
|
|
| (13) | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 50 |
|
|
|
|
| |
|
|
|
|
|
|
| (10) |
|
| C |
| ||
|
|
|
| 45 |
|
|
|
|
| ||||
|
|
|
| D |
|
|
| ||||||
|
|
|
| (7) |
|
|
|
|
|
|
| ||
|
| 40 |
|
|
|
|
|
|
|
|
|
| |
|
| (4) |
|
|
|
|
|
|
|
|
|
| |
| 35 |
|
|
|
|
|
|
|
|
|
|
|
|
| (2) |
|
|
|
|
|
|
|
|
|
|
|
|
40
AIR | 38 |
36 |
|
65
(18)
60
(16)
A
B
|
| 46 |
|
| 44 |
|
|
42 |
|
| 80 |
|
| (27) | |
|
| 75 |
|
|
| (24) |
|
70 |
|
| |
(21) |
|
| |
100 | 90 | 80 |
|
|
| ||
|
| 70 | |
|
|
| |
|
|
| 60 |
D C B
85 | 90 | 95 | 100 | 105 | 110 |
(29) | (32) | (25) | (38) | (41) | (43) |
HUMIDITY | (%) |
| |
RELATIVE |
|
50 40
30
20
10
A
N1 |
| EXH | TR |
N |
| Set |
|
2V | 10V |
| |
|
| ||
P1 | EXH |
| 24 |
|
| Vac | |
|
|
| |
P |
| Min | HOT |
T1 |
| Pos |
|
|
|
| |
T |
| Open |
|
|
|
| |
|
| DCV | 1 |
|
| Max | |
|
|
| |
| 2V | 10V |
|
AQ+ | DCV |
|
|
|
|
| |
AQ |
| DCV |
|
SO+ |
| Set | 3 |
|
|
| |
SO | 2V | 10V |
|
|
|
| |
SR+ | Free |
| EF |
Cool |
|
| |
|
|
| |
SR | B | C |
|
|
|
| |
| A | D |
|
Fig. 44 - Economizer Controller
TR1
24Vac
COM
2
5
4
EF1
A09712
607C-- -- A
35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | 105 | 110 |
(2)(4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (36) (38) (41) (43)
APPROXIMATE DRY BULB TEMPERATURE — ˚F (˚C)
A09711
Fig. 42 - Enthalpy Changeover Setpoints
6000 |
|
|
|
|
|
|
5000 |
|
|
|
|
|
|
4000 |
|
|
|
|
| 800 ppm |
|
|
|
|
|
| |
3000 |
|
|
|
|
| 900 ppm |
|
|
|
|
| 1000 ppm | |
|
|
|
|
|
| |
2000 |
|
|
|
|
| 1100 ppm |
|
|
|
|
|
| |
1000 |
|
|
|
|
|
|
0 |
|
|
|
|
|
|
2 | 3 | 4 | 5 | 6 | 7 | 8 |
|
|
|
|
|
| A09713 |
Fig. 43 - CO2 Sensor Maximum Range Setting
OUTDOOR ENTHALPY
When the outdoor air enthalpy rises above the outdoor enthalpy changeover set point, the
42.The
DIFFERENTIAL ENTHALPY CONTROL — For differential enthalpy control, the Economizer controller uses two enthalpy sensors (HH57AC078 and CRENTDIF004A00), one in the outside air and one in the return airstream. The Economizer controller compares the outdoor air enthalpy to the return air enthalpy to determine Economizer use. The controller selects the lower enthalpy air (return or outdoor) for cooling. For example, when the outdoor air has a lower enthalpy than the return air and is below the set point, the Economizer opens to bring in outdoor air for free cooling. Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location. Mount the return air enthalpy sensor in the return air duct. See Fig. 41. When using this mode of changeover control, turn the enthalpy set point poten- tiometer fully clockwise to the D setting.
INDOOR AIR QUALITY (IAQ) SENSOR INPUT
EXHAUST SET POINT
MINIMUM POSITION CONTROL — There is a minimum damper position potentiometer on the Economizer controller. See Fig. 39 and 45. The minimum damper position maintains the minimum airflow into the building during the occupied period. When using demand ventilation, the minimum damper position represents the minimum ventilation position for VOC (volatile organic compound) ventilation requirements. The DCV Max potentiometer must be fully closed (CCW) to allow the Minimum Position potentiometer to function correctly.
39