APPLICATION DATA (cont)
3)For line lengths over 50 ft (018,024 only):
a)A crankcase heater should be added to scroll compressor units (all
b)Any time the equivalent line length is over 100 ft, a liquid line solenoid must be used. A liquid line solenoid may also be required for vertical lift ap- plications over 25 ft. See Step h) on page 22.
c)The accessory wind baf¯e is recommended.
d)The Effective Capacity Loss table on this page provides the estimated percentage of nominal cooling capacity losses based on the standard re- quired vapor line size versus what is selected for
Select the desired vapor line size from the Effec- tive Capacity Loss table based on equivalent ft and desired vapor line size.
Subtract the nominal percentage loss from the unit cooling capacities for the given indoor and outdoor combination.
FITTING LOSS IN EQUIVALENT FT FOR ELBOWS
TUBE SIZE | ||||
SHORT | LONG | SHORT | ||
O.D. (in.) | ||||
RADIUS | RADIUS | RADIUS | ||
| ||||
5¤8 | 1.6 | 1.0 | 0.8 | |
3¤4 | 1.8 | 1.2 | 0.9 |
CHATTLEFF COMMON PISTON SIZES
PISTON SIZE | PISTON SIZE | PISTON SIZE |
32 | 53 | 80 |
33 | 55 | 81 |
35 | 57 | 82 |
36 | 59 | 84 |
37 | 61 | 86 |
38 | 62 | 88 |
39 | 63 | 89 |
40 | 65 | 90 |
41 | 67 | 92 |
42 | 68 | 93 |
43 | 70 | 96 |
45 | 71 | 98 |
47 | 73 | 101 |
49 | 74 | 104 |
51 | 76 | Ð |
52 | 78 | Ð |
|
|
|
COOLING ONLY SYSTEM PISTON GUIDE AND REFRIGERANT CHARGES
INDOOR | OUTDOOR | PISTON REQUIRED | CHARGE | |||||
UNIT | UNIT | |||||||
(Size) | (Lb)* | |||||||
619E |
|
|
| 538 | ||||
|
|
|
|
| ||||
|
|
|
|
|
|
|
| |
009 |
| C |
| 009 | None | 1.5 | ||
|
|
|
|
|
|
|
| |
012 |
| C |
| 012 | None | 1.8 | ||
|
|
|
|
|
|
|
| |
018 |
| A |
| 018 | 49 | 4.6 | ||
|
|
|
|
|
|
|
| |
024 |
| A |
| 024 | 57 | 5.3 | ||
|
|
|
|
|
|
|
|
*Charge based on 25 ft of interconnecting tubing. Charge may need to be added for longer tubing runs or when used with certain fan coils. Check unit nameplate for required charge.
NOTES:
1.All 018,024 pistons are Chattleff type.
2.All cooling units have a full factory charge.
3.Service valves are
HEAT PUMP SYSTEM PISTON GUIDE AND REFRIGERANT CHARGES
|
| UNIT | COOLING | HEATING | REQUIRED | |||
Indoor |
| Outdoor | PISTON | PISTON | SYSTEM | |||
619E |
|
| 538D |
|
| SIZE | SIZE | CHARGE (Lb)* |
|
|
|
|
|
|
|
|
|
009 |
| 009 |
| 30 | 32 | 1.5 | ||
012 |
| 012 |
| 42 | 42 | 2.0 | ||
018 |
| 018 |
| 51 | 47 | 5.0 | ||
024 |
| 024 |
| 49 | 52 | 5.1 |
*Charge based on 25 ft of interconnecting tubing. Charge may need to be added for longer tubing runs or when used with certain fan coils. Check unit nameplate for required charge.
NOTES:
1.All 009,012 pistons are Aeroquip type. All 018,024 pistons are Chattleff type.
2.The 538D heat pumps have a holding charge only as shipped from the factory.
EFFECTIVE CAPACITY LOSS
NOMINAL | STANDARD |
|
| PERCENT COOLING CAPACITY LOSS |
|
| ||||
UNIT SIZE* | VAPOR LINE (in.) | VAPOR LINE (in.)² | 50 ft | 75 ft | 100 ft | 125 ft | 150 ft |
| 175 ft | 200 ft |
18,000 | 5¤8 | 5¤8 | 1 | 3 | 4 | 5 | 7 |
| 9 | 10 |
5¤8 | 3¤4 | 0 | 0 | 1 | 1 | 2 |
| 2 | 3 | |
|
| |||||||||
24,000 | 5¤8 | 5¤8 | 2 | 5 | 8 | 10 | 13 |
| ** | ** |
5¤8 | 3¤4 | 0 | 0 | 1 | 2 | 3 |
| 4 | 5 | |
|
|
*Nominal cooling capacity of the unit being speci®ed.
²The vapor line diameter that may be selected for
**Not recommended due to excessive loss of capacity.
NOTE:
21