Bryant 619E manual Fitting Loss In Equivalent Ft For Elbows, Chattleff Common Piston Sizes

Models: 619E

1 32
Download 32 pages 7.08 Kb
Page 21
Image 21
FITTING LOSS IN EQUIVALENT FT FOR ELBOWS

APPLICATION DATA (cont)

3)For line lengths over 50 ft (018,024 only):

a)A crankcase heater should be added to scroll compressor units (all non-scroll compressor units have crankcase heaters as standard). Crankcase heaters help prevent refrigerant migration to the compressor during the off cycle.

b)Any time the equivalent line length is over 100 ft, a liquid line solenoid must be used. A liquid line solenoid may also be required for vertical lift ap- plications over 25 ft. See Step h) on page 22.

c)The accessory wind baf¯e is recommended.

d)The Effective Capacity Loss table on this page provides the estimated percentage of nominal cooling capacity losses based on the standard re- quired vapor line size versus what is selected for long-line applications.

Select the desired vapor line size from the Effec- tive Capacity Loss table based on equivalent ft and desired vapor line size.

Subtract the nominal percentage loss from the unit cooling capacities for the given indoor and outdoor combination.

FITTING LOSS IN EQUIVALENT FT FOR ELBOWS

TUBE SIZE

90-DEGREE

90-DEGREE

45-DEGREE

SHORT

LONG

SHORT

O.D. (in.)

RADIUS

RADIUS

RADIUS

 

5¤8

1.6

1.0

0.8

3¤4

1.8

1.2

0.9

CHATTLEFF COMMON PISTON SIZES

PISTON SIZE

PISTON SIZE

PISTON SIZE

32

53

80

33

55

81

35

57

82

36

59

84

37

61

86

38

62

88

39

63

89

40

65

90

41

67

92

42

68

93

43

70

96

45

71

98

47

73

101

49

74

104

51

76

Ð

52

78

Ð

 

 

 

COOLING ONLY SYSTEM PISTON GUIDE AND REFRIGERANT CHARGES

INDOOR

OUTDOOR

PISTON REQUIRED

CHARGE

UNIT

UNIT

(Size)

(Lb)*

619E

 

 

 

538

 

 

 

 

 

 

 

 

 

 

 

 

 

009

 

C

 

009

None

1.5

 

 

 

 

 

 

 

 

012

 

C

 

012

None

1.8

 

 

 

 

 

 

 

 

018

 

A

 

018

49

4.6

 

 

 

 

 

 

 

 

024

 

A

 

024

57

5.3

 

 

 

 

 

 

 

 

*Charge based on 25 ft of interconnecting tubing. Charge may need to be added for longer tubing runs or when used with certain fan coils. Check unit nameplate for required charge.

NOTES:

1.All 018,024 pistons are Chattleff type.

2.All cooling units have a full factory charge.

3.Service valves are front-seating type.

HEAT PUMP SYSTEM PISTON GUIDE AND REFRIGERANT CHARGES

 

 

UNIT

COOLING

HEATING

REQUIRED

Indoor

 

Outdoor

PISTON

PISTON

SYSTEM

619E

 

 

538D

 

 

SIZE

SIZE

CHARGE (Lb)*

 

 

 

 

 

 

 

 

 

009

 

009

 

30

32

1.5

012

 

012

 

42

42

2.0

018

 

018

 

51

47

5.0

024

 

024

 

49

52

5.1

*Charge based on 25 ft of interconnecting tubing. Charge may need to be added for longer tubing runs or when used with certain fan coils. Check unit nameplate for required charge.

NOTES:

1.All 009,012 pistons are Aeroquip type. All 018,024 pistons are Chattleff type.

2.The 538D heat pumps have a holding charge only as shipped from the factory.

EFFECTIVE CAPACITY LOSS

NOMINAL

STANDARD

LONG-LINE

 

 

PERCENT COOLING CAPACITY LOSS

 

 

UNIT SIZE*

VAPOR LINE (in.)

VAPOR LINE (in.)²

50 ft

75 ft

100 ft

125 ft

150 ft

 

175 ft

200 ft

18,000

5¤8

5¤8

1

3

4

5

7

 

9

10

5¤8

3¤4

0

0

1

1

2

 

2

3

 

 

24,000

5¤8

5¤8

2

5

8

10

13

 

**

**

5¤8

3¤4

0

0

1

2

3

 

4

5

 

 

*Nominal cooling capacity of the unit being speci®ed.

²The vapor line diameter that may be selected for long-line application. If smaller vapor lines than are speci®ed in the table are selected, a larger capacity loss will occur. If larger vapor lines are selected, refrigerant oil return will be impaired due to velocity loss.

**Not recommended due to excessive loss of capacity.

NOTE: Long-line applications (50 ft and longer) are not permitted on 009, 012 systems.

21

Page 21
Image 21
Bryant 619E manual Fitting Loss In Equivalent Ft For Elbows, Chattleff Common Piston Sizes, Effective Capacity Loss