SPECIFICATIONS Ð 538D HEAT PUMP UNITS

UNIT 538D

 

 

009

 

012

018

024

 

 

 

 

 

 

 

 

NOMINAL CAPACITY (Tons)

3¤4

 

1

11¤2

2

OPERATING WEIGHT (lb)

60.7

 

66.6

154

167

REFRIGERANT TYPE

 

 

 

R-22

 

Control (Cooling)

Fixed Ori®ce at Outdoor Unit

AccuRater Piston at Fan Coil Unit

Control (Heating)

Fixed Ori®ce at Outdoor Unit

AccuRater Piston at Outdoor Unit

Factory Charge (lb)*

1.5

 

2.0

5.0

5.1

COMPRESSOR TYPE

Carlyle Rotary

Tecumseh Reciprocating

Model

EBA095111H

 

EBB130111H

AW5519G

AW5524G

OUTDOOR FAN

Propeller Type

Propeller, Direct Drive

Rpm (Cooling and Heating)

1050

 

1050

850

850

Nominal Air Cfm (High Speed)

Ð

 

Ð

1720

1720

OUTDOOR COIL

 

 

Copper Tube, Aluminum Fin

 

Face Area (sq ft)...No. of Rows

3.5...1

 

3.5...2

6.1...1.5

6.1...2

Fins/in.

18

 

18

15

15

CONTROLS

 

 

 

 

 

High-Pressure (psig)

 

 

 

 

 

Cutout

Ð

 

Ð

320 ± 20

Cut-in

Ð

 

Ð

426 ±

7

Liquid Line Low-Pressure (psig)

 

 

 

 

 

Cutout

Ð

 

Ð

7 ±

3

Cut-in

Ð

 

Ð

22 ±

5

Fusible Plug

210 F

 

210 F

210 F

Defrost Method²

Time and Temperature Defrost

Time and Temperature Defrost

Accumulator

Yes

 

Yes

Yes

Control Voltage**

115

 

230

24

REFRIGERANT LINES

 

 

 

 

 

Connection Type

 

Flare

SweatÐSuction; FlareÐLiquid

Mixed Phase Line OD (in.)

1¤4

 

1¤4

3¤8

3¤8

Suction Line OD (in.)

1¤2

 

1¤2

5¤8

5¤8

Maximum Length (ft)

35

 

35

200

200

Maximum Lift (Fan Coil Above Outdoor) (ft)

16

 

16

65

65

Maximum Lift (Fan Coil Below Outdoor) (ft)

30

 

30

150

150

EXTERNAL FINISH

 

Grey

Alpine Mist (Beige)

 

 

 

 

 

 

 

 

*Units are shipped with charge listed (smallest applicable system charge). Refer to Piston Guide tables on page 21 for proper charge for your application.

²Demand defrost.

**A 24-v transformer is provided in the 018, 024 fan coil unit.