APPLICATION DATA

1.Unit selection

Select equipment to either match or be slightly less than an- ticipated peak load. This provides better humidity control, fewer unit cycles, and less part-load operation.

For units used in spaces with high sensible loads, base equipment selection on unit sensible load, not on total an- ticipated load. Adjust for anticipated room wet bulb tem- perature to avoid undersizing equipment.

For heat pump systems, heating load using outdoor air must be checked in addition to cooling load. Heating load of outdoor air can greatly reduce heating capability.

For heat pump systems, heating and cooling design loads must both be checked.

When selecting equipment which has outdoor air intro- duced into the unit, determine the mix conditions of room air and outdoor air at design conditions. The cooling capacity tables in this literature are based on 80 F edb. Adjust for ac- tual dry-bulb and wet-bulb conditions with the required out- door air to select the proper equipment.

2.Unit combinations and coil mixed matches

The 538A, 538C, 538D, and 538S units are the only units approved for use with the 619E duct-free split systems. These outdoor units may also be used with other fan coil units.

3.Unit mounting (outdoor)

a.Unit leveling Ð For reliable operation, units should be level in all planes.

b.Clearance Ð Adequate clearance must be provided for air¯ow. See dimensional drawings for proper clear- ances. The outdoor units are designed for free-blow ap- plication. Air inlets and outlets should not be restricted. Outdoor fan external static pressure available is less than 0.1 in. wg.

c.Unit location Ð Cooling units may be stacked 2 high. Units may be wall mounted, pad mounted at ground level, roof mounted, mounted on or under a deck, or mounted on a patio. Be sure water drainage from roof will not drain directly onto the unit.

NOTE: If stacking units is desired (538A, 538C, 538S only), ®eld-fabricated and installed hardware is required. Contact your local representative for details.

If 018, 024, 048 units are being mounted near a wall, the outdoor-air section should discharge toward the wall. This will provide inherent coil protection and the best possible sound and air¯ow performance. The 009, 012 units should be mounted with fan discharge pointing away from the wall.

4.Unit mounting (indoor)

a.Unit leveling Ð For reliable operation, units should be level in all planes.

b.Clearance Ð Provide adequate clearance for air¯ow. The unit return and discharge should not be obstructed by furniture, curtains, or anything which may cause unit short cycling or air recirculation. See base unit dimen- sional drawings on pages 13 and 14 for required clearances.

c.Unit location Ð When selecting unit location, select a location which will provide the best air circulation for the room.

Position units as high as possible on the wall for best air circulation. Allow adequate clearances above the unit for servicing (removing unit covers). Place the unit in the middle (horizontally) of the wall selected (if possible). Select an outside wall if available to make piping easier, and place the unit so it faces the normal location of room occupants.

5.Mounting template

The fan coil units are furnished with a mounting template to mark the location of the mounting brackets, wiring, and re- frigeration hole locations.

6.Support

Adequate support must be provided to support the weight of all fan coils. Refer to the Speci®cation tables on page 8 for fan coil weights, and the base unit dimensional drawings on pages 13 and 14 for the location of mounting brackets.

7.System operating conditions Operating limits:

OUTDOOR UNITS

CONDITION

009,012

018,024,048

Maximum Cooling Ambient (F)

125

125

Minimum Cooling Ambient (F) (without

55

55

accessory low-ambient kit)

 

 

Minimum Cooling Ambient (F) (with

±20

±20

accessory low-ambient kit)

 

 

Minimum Cooling Return-Air Temperature (F)

55

55

Maximum Cooling Return-Air Temperature (F)

95

95

Maximum Heating Return-Air Temperature (F)*

80/71²

80/71²

Minimum Heating Return-Air Temperature (F)*

55

55

Maximum Heating Ambient Temperature (F)*

0

−20

Minimum Heating Ambient Temperature (F)

80

80

Saturated Suction Temperature Range

 

 

Minimum (F)

±15

±15

Maximum (F)

55

55

Saturated Condensing Temperature Range

 

 

Minimum (F)

85

80

Maximum (F)

150

150

Maximum Compressor Discharge

275

275

Temperature (F)

 

 

Minimum Discharge Superheat (F)

60

60

 

 

 

*Heat pump units only.

 

 

²Dry bulb/wet bulb.

 

 

FAN COIL UNITS

 

 

CONDITION

ALL

UNITS

 

Maximum Room

84

Temperature (F)

 

Minimum Room

64

Temperature (F)

 

Maximum Return Air (F)

 

Dry-Bulb

85

Wet-Bulb

72

Maximum Saturated

55

Suction Temperature (F)

 

Minimum Saturated

27

Suction Temperature (F)

 

8.Low-ambient operation

Units can operate in cooling down to 55 F (538A, 538C, 538D) under all conditions without a low-ambient or winter start kit.

Units equipped with accessory low-ambient or winter start kits should also be equipped with ®eld-fabricated wind baffle, ®eld supplied crankcase heater (scroll units only) and ®eld-supplied isolation relay.

a.Winter start (538C and 538S) Ð The use of a winter start control may extend the unit operation range (below 40 F) without addition of the low-ambient kit. Winter start bypasses the low-pressure switch for 3 minutes.

b.Crankcase heater Ð Scroll compressor units with low- ambient control or winter start should be equipped with crankcase heaters to prevent refrigerant migration dur- ing compressor off cycle.

c.Freezestat (heat pump systems only) Ð Freeze up protection is provided on all fan coil units.

19

Page 19
Image 19
Bryant 619E manual Application Data, Outdoor Units, Condition ALL Units