Bryant 619E manual Air Throw Data, Condensing Unit Sound Ratings, Group control, Wiring, Air throw

Models: 619E

1 32
Download 32 pages 7.08 Kb
Page 23
Image 23

APPLICATION DATA (cont)

j)Elevated con®guration Ð Indoor unit installed above the outdoor unit (see ®gure at right):

·If there is over 25 ft of lift, a bi¯ow (538D only) or standard solenoid valve is required in the liquid line.

·The maximum elevation difference is 65 ft, and the maximum equivalent ft of piping is 200.

·Install an inverted trap in the vapor line. The top of the trap must be above the top of the fan coil. This prevents the refrigerant from collecting in the vapor line.

k)Lowered con®guration Ð Indoor unit installed below the outdoor unit (see ®gure at right):

·For lines shorter than 100 ft, no solenoid valve is required in the liquid line. For lines over 100 ft, in- stall a bi¯ow (538D only) or standard solenoid valve in the liquid line.

·The maximum elevation difference is 150 ft, and the maximum equivalent ft is 200.

l)Additional charge Ð The unit should be charged by weighing in the appropriate charge. Add charge based on the actual length of line which is over 25 ft of liquid line. Add .58 oz of refrigerant per 1 ft in- crease over the 25 ft line to the charge listed in Sys- tem Piston Guide and Refrigerant Charges table on page 21.

NOTE: This only applies to systems where the piston is located at the indoor unit (538A018,024 and 538D018,024).

12.Group control

The 619E fan coil units may be group controlled from a single timeclock or energy management system by inter- rupting the 24-v power to the control board.

13.Thermistors (Heat Pump Systems Only)

Thermistors are used on both indoor and outdoor units to determine operating conditions. Proper thermistor location is critical to unit operation. All thermistors have identical re- sistance values. See Thermistor Equivalence charts on typical system wiring schematics (pages 24-27).

Thermistor cable assemblies are provided with fan coil units to run between indoor and outdoor units. High-voltage

and thermistor cable assemblies should not touch each other, and cable runs may be extended up to 200 ft.

14.Wiring

Use only copper wires from the disconnect to the unit ter- minal block. Aluminum and copper-clad aluminum wires are not acceptable.

All duct-free split systems (except the 009,012 outdoor units) provide 24-v power for the outdoor unit in the duct- free fan coil. The 009,012 outdoor units systems use high- voltage controls.

The 009,012 outdoor units system fan coil units must have power wires run from the outdoor condensing unit to the in- door unit to prevent out-of-phase wiring.

15.Air throw

Refer to Air Throw Data table below for system air throw

capabilities.

AIR THROW DATA*

FAN COIL

HIGH SPEED

APPROXIMATE

SIZE

CFM

AIR THROW (FT)

009

215/252*

16

012

302

24

018

480/455*

30

024

550/525*

35

 

 

 

*Cooling only unit/Heat pump unit.

NOTE: Air throw is with unit mounted with typical clearances in a 10-ft high room.

16.Sound data

CONDENSING UNIT SOUND RATINGS

UNIT SIZE

SOUND RATING (Decibels)

FREE FIELD dBA*

 

 

 

 

009

 

66

55.7

012

 

66

55.7

018

 

68

57.7

024

 

68

57.7

 

 

 

 

 

 

 

LEGEND

 

Decibels

Ð

Sound levels

 

dBA

Ð

Decibels on the A Scale

 

*Free ®eld is a rating with no re¯ective surfaces near the unit. Data sound pressure is measured at 3.2 ft (1 m) from the unit. See Sound Power Data Octave Bands table for more information.

SOUND POWER DATA OCTAVE BANDS Ð A WEIGHTED (Fan Coil Units Only)

UNIT

FAN SPEED

 

 

 

OCTAVE BAND DATA (dBA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

125

250

500

 

1000

 

2000

4000

8000

619F

 

009

High

36.5

40.3

45.2

 

48.2

 

42.3

33.2

31.2

Cooling

Medium

32.8

37.9

43.6

 

44.9

 

39.1

29.8

31.2

Only

 

 

 

 

 

 

 

 

 

 

Low

31.7

36.6

41.6

 

41.6

 

35.4

27.7

31.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

619F

 

009

High

38.2

41.1

46.2

 

47.9

 

43.0

33.6

31.2

Heat

 

Medium

31.7

39.8

45.0

 

45.3

 

42.0

36.8

36.8

Pump

 

 

 

 

 

 

 

 

 

 

Low

29.2

38.4

43.9

 

41.9

 

38.6

28.1

31.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

619F

 

012

High

36.7

43.5

50.2

 

51.1

 

46.5

38.6

31.7

Cooling

Medium

33.6

42.5

47.1

 

48.8

 

43.4

36.2

33.4

Only

 

 

 

 

 

 

 

 

 

 

Low

33.5

41.6

43.8

 

45.6

 

39.8

33.0

32.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

619F

 

012

High

35.1

43.8

50.3

 

51.1

 

46.4

38.0

31.2

 

 

 

 

 

 

 

 

 

 

 

Heat

 

Medium

31.7

43.3

46.3

 

48.6

 

42.9

34.2

31.2

Pump

 

 

 

 

 

 

 

 

 

 

Low

29.1

42.2

42.9

 

45.6

 

39.1

30.3

31.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

619F

 

018

High

40.8

49.1

53.7

 

55.2

 

49.1

41.3

32.3

 

 

 

 

 

 

 

 

 

 

 

Cooling

Medium

38.0

46.7

50.6

 

51.7

 

44.9

35.8

31.6

Only

 

 

 

 

 

 

 

 

 

 

Low

37.3

44.4

47.5

 

48.6

 

40.4

32.0

31.6

 

 

 

 

 

619F

 

018

High

37.0

44.4

49.3

 

50.4

 

43.4

35.6

31.9

 

 

 

 

 

 

 

 

 

 

 

Heat

 

Medium

39.8

46.9

52.2

 

53.7

 

47.4

40.1

32.7

Pump

 

 

 

 

 

 

 

 

 

 

Low

43.2

49.1

54.0

 

56.0

 

50.7

44.0

34.0

 

 

 

 

 

619F

 

024

High

44.9

51.9

59.1

 

59.5

 

54.8

48.0

36.7

 

 

 

 

 

 

 

 

 

 

 

Cooling

Medium

43.7

50.5

57.2

 

57.0

 

51.8

44.4

33.6

Only

 

 

 

 

 

 

 

 

 

 

Low

40.7

47.7

55.1

 

54.7

 

49.0

40.5

32.2

 

 

 

 

 

619F

 

024

High

43.8

51.5

58.5

 

58.8

 

53.5

46.2

36.0

 

 

 

 

 

 

 

 

 

 

 

Heat

 

Medium

41.4

49.5

56.5

 

56.2

 

50.4

42.5

36.0

Pump

 

 

 

 

 

 

 

 

 

 

Low

38.9

47.3

54.4

 

53.7

 

47.4

39.0

36.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

ARI

Ð

Air Conditioning & Refrigeration Institute

dBA

Ð

Decibels on the A scale

NOTES:

1.Outdoor sound levels are tone corrected values taken in accordance with ARI Sound Standard 270.

2.Indoor sound levels are tone corrected values taken in accordance with ARI Sound Standard 350.

23

Page 23
Image 23
Bryant 619E manual Air Throw Data, Condensing Unit Sound Ratings, Group control, Thermistors Heat Pump Systems Only, Wiring