Bryant BW3 Dimensions, Clearances, Ratings and Capacities, Unit Type Btuh Capacity Btuh Afue %

Models: BW1 BS1 BW9 BW4B BW5B BW3 BS2 BW2

1 16
Download 16 pages 33.61 Kb
Page 6
Image 6

DIMENSIONS

MODEL BW9

ALTERNATE SUPPLY

&RETURN OPENINGS (1-1/4" NPT (31.75mm)

CONNECTIONS

PROVIDED INSIDE

BOILER CABINET)

ACCESS PANEL

GAS SUPPLY

OPENING

(1/2" NPT) (12.7mm)

COMBUSTION AIR

INTAKE FITTING

(2" PVC) (50.8mm)

ALTERNATE OPENING

FOR GAS SUPPLY

BOILER WATER TEMPERATURE & PRESSURE GAUGE

FRONT PANEL DOOR PULL

LEVELING FEET

JUNCTION BOX FOR 120 V POWER, 120 V CIRCULATOR BEADS, AND 24 V THERMOSTAT LEADS

VENT CONNECTION

(2" CPVC) (50.8mm)

ALTERNATE GAS

SUPPLY OPENING

ALTERNATE OPENING FOR

VENT TEE

A99156

STANDARD BOILER WATER

SUPPLY & RETURN OPENINGS

(1-1/4" NPT (31.75mm) CONNECTIONS PROVIDED INSIDE BOILER CABINET)

5" (127mm)

VENT CONNECTION

(2" CPVC) (50.8mm)

DRAIN

CONDENSATE

DRAIN FITTING

(1/2" PVC) (12.7mm)

OPENING FOR RELIEF VALVE

DISCHARGE PIPE

OPENING FOR AIR

VENT AND EXPANSION

TANK CONNECTION

ALTERNATE BOILER WATER SUPPLY AND

RETURN

(31.75mm) CONNECTIONS

(1-1/4" NPT

BOILER CABINET)

PROVIDED INSIDE

CLEARANCES

UNIT

COMBUSTIBLE (in.)

ACCESSIBILITY/CLEANING (in.)

SERVICING (in.)

 

 

 

 

TOP

1

8

8

 

 

 

 

LEFT SIDE

1

24

24

RIGHT SIDE

8

 

 

 

 

BASE

1

FRONT

0

24

24

BACK

1

 

 

 

 

INTAKE/VENT PIPING

0

NEAR BOILER HOT WATER PIPING

1

*Service clearance requirement 24-in.

RATINGS AND CAPACITIES*

 

 

 

 

 

 

BOILER

 

 

 

 

 

 

 

WATER

APPROX

 

GAS

MAX INPUT

HEATING

 

NET RATING

CAPACITY

SHIP.

UNIT

TYPE

(BTUH)

CAPACITY (BTUH)

AFUE %

Btuh†

(GALLONS)

WT (Lb)

BW9AAN050

Natural

50,000

45,000

90

39,000

2.6

220

BW9AAN075

Natural

75,000

68,000

90

59,000

2.6

220

 

 

 

 

 

 

 

 

BW9AAN100

Natural

100,000

90,000

90

78,000

2.6

220

*Gas input ratings are for elevations up to 2000 ft. In the USA, for elevations above 2000 ft., reduce input per the charts supplied in the high altitude derate kits. In Canada, boilers may be used at high altitude by using a certified field conversion kit.

—6—

Page 6
Image 6
Bryant BW3, BW4B, BS1, BW1, BS2 Dimensions, Clearances, Ratings and Capacities, Unit Type Btuh Capacity Btuh Afue %, Gallons