DIMENSIONS

BW3 MODELS

RELIEF

A

TEMP

VALVE

PRESSURE

 

 

GAGE

 

29

 

5 58

BURNER

1 34

 

7

1 14SUPPLY

COMBINATION 23 14

LIMIT & RELAYVENT

CONTROLCONNECTOR

1 14RETURN

 

 

BLOWER

25 14

 

23

PRESSURE

 

5 58

SWITCH

 

 

CIRCULATOR

GAS

INT. PILOT

VALVE

CONTROL

LEFT SIDE

FRONT

RIGHT SIDE

DIMENSIONS (In.)

UNIT SIZE

A

VENT CONNECTION

042

11

4*

075

14-1/4

4*

112

17-1/2

4*

 

 

 

150

20-3/4

4*

187

24

4*

225

27-1/4

4*

 

CLEARANCES (In.)

 

 

RIGHT SIDE

 

6*

LEFT SIDE

 

6

TOP

 

6

BACK

 

6

 

 

 

FRONT

 

6*

*Service clearance requirement 24 in.

*With factory-supplied adapter installed.

RATINGS AND CAPACITIES*

 

 

 

RATINGS

 

 

BOILER

 

 

 

 

HEATING

 

 

 

 

 

 

 

 

WATER

APPROX

 

 

 

CAPACITY‡

 

NET RATING

 

GAS

MAX INPUT

 

CAPACITY

SHIP.

 

 

 

 

UNIT

TYPE

(BTUH)

Btuh

AFUE %

Btuh†

(GALLONS)

WT (Lb)

 

 

 

 

 

 

 

 

BW3AAN042

Natural

42,500

36,000

84.4

31,000

1.75

211

BW3AAN075

Natural

75,000

63,000

83.4

55,000

3.00

263

 

 

 

 

 

 

 

 

BW3AAN112

Natural

112,500

94,000

83.0

82,000

4.25

320

BW3AAN150

Natural

150,000

125,000

82.7

109,000

5.50

369

BW3AAN187

Natural

187,500

155,000

82.3

135,000

6.75

418

*Gas input ratings are for elevations up to 2000 ft. For elevations above 2000 ft, reduce input 4% for each 1000 ft above sea level.

Selection factors providing for piping loss and starting load are those recommended by the Institute of Boiler and Radiator Manufacturers. Net water boiler ratings are based on an allowance of 1.15.

In accordance with U.S. Government test procedures.

—12—

Page 12
Image 12
Bryant BW5B, BW4B, BS1, BW1, BS2, BW2, BW9 manual BW3 Models, Unit Type Btuh