DIMENSIONS

 

 

 

 

MODELS BS1 and BS2

 

 

VENT

PRESSURE

 

 

DAMPER

26 12

 

RELIEF

 

GAGE

 

 

 

4 34

 

VALVE

 

 

2 12

 

 

TRANSFORMER

 

 

 

 

 

 

 

PRESSURE

 

GLASS

 

 

 

GAGE

 

 

LIMIT CONTROL

 

WATER

2 12N.P.T.

 

LOW WATER

 

 

 

LINE

 

 

CUT-OFF

 

 

29

36 38

LOW WATER

2 12

24

 

 

 

CUT-OFF PROBE

S86

 

12 14

 

 

GAS

 

 

 

 

 

 

 

 

VALVE

 

 

 

GAS LINE

 

 

 

 

A

 

 

LEFT SIDE

 

FRONT

RIGHT SIDE

 

DIMENSIONS (In.)

UNIT SIZE

A

VENT DIAMETER

 

 

 

075

11-1/4

5

 

 

 

112

14-1/2

6

150

17-3/4

6

187

21

7

 

 

 

225

24-1/4

7

262

27-1/2

7

299

30-3/4

7

 

CLEARANCES (In.)

 

 

RIGHT SIDE

 

6*

LEFT SIDE

 

6*

TOP

 

6*

BACK

 

6*

FRONT

 

6*

*Service clearance requirement 24 in.

RATINGS AND CAPACITIES*

 

GAS

NUMBER

MAX

HEATING

NET RATING

 

APPROX

 

OF

INPUT

CAPACITY

 

 

AFUE %

SHIP.

 

 

 

UNIT

TYPE

SECTIONS

(BTUH)

(BTUH)

Btuh

Sq Ft

(WITH DAMPER)

WT (Lb)

 

 

 

 

 

 

 

 

 

BS1AAN075

Natural

3

75,000

62,000

47,000

196

81.1

256

BS1AAN112

Natural

4

112,500

91,000

68,000

283

78.8

404

 

 

 

 

 

 

 

 

 

BS1AAN150

Natural

5

150,000

122,000

92,000

383

79.2

483

 

 

 

 

 

 

 

 

 

BS1AAN187

Natural

6

187,500

153,000

115,000

479

79.6

564

BS1AAN225

Natural

7

225,000

183,000

137,000

571

80.1

649

 

 

 

 

 

 

 

 

 

BS1AAN262

Natural

8

262,500

214,000

161,000

671

80.5

719

 

 

 

 

 

 

 

 

 

BS1AAN299

Natural

9

299,000

245,000

184,000

767

80.9

800

BS2AAN075

Natural

3

75,000

62,000

47,000

196

82.7

256

 

 

 

 

 

 

 

 

 

BS2AAN112

Natural

4

112,500

91,000

68,000

283

80.4

404

 

 

 

 

 

 

 

 

 

BS2AAN150

Natural

5

150,000

122,000

92,000

383

80.6

483

BS2AAN187

Natural

6

187,500

153,000

115,000

479

80.9

564

 

 

 

 

 

 

 

 

 

BS2AAN225

Natural

7

225,000

183,000

137,000

575

81.1

649

 

 

 

 

 

 

 

 

 

BS2AAN262

Natural

8

262,500

214,000

161,000

671

81.3

719

BS2AAN299

Natural

9

299,000

245,000

184,000

767

81.6

800

 

 

 

 

 

 

 

 

 

*Ratings are for altitudes to 2000 ft. Ratings for units for altitudes over 2000 ft are 4% less for each 1000 ft above sea level. Ratings in sq ft are computed at 240 Btuh/sq ft for steam boilers.

—8—

Page 8
Image 8
Bryant BW4B, BW1, BW5B, BW2, BW3, BW9 manual Models BS1 and BS2, Unit Size Vent Diameter