GT-PG (50YE) Series

Air Flow Correction Factors

PSC Fan Motor

Airflow

 

 

Cooling

 

 

 

Heating

 

% of

Total

Sensible

S/T

Power

Heat of

Heating

Power

Heat of

Rated

Capacity

Capacity

Rejection

Capacity

Extraction

 

 

 

68.75%

0.9465

0.8019

0.8472

0.9614

0.9496

 

 

 

75%

0.9602

0.8350

0.8696

0.9675

0.9617

0.9740

1.0936

0.9425

 

 

 

 

 

 

 

 

 

81.25%

0.9724

0.8733

0.8981

0.9744

0.9728

0.9810

1.0635

0.9592

 

 

 

 

 

 

 

 

 

87.50%

0.9831

0.9149

0.9306

0.9821

0.9829

0.9876

1.0379

0.9744

93.75%

0.9923

0.9578

0.9653

0.9906

0.9920

0.9940

1.0167

0.9880

 

 

 

 

 

 

 

 

 

100%

1.0000

1.0000

1.0000

1.0000

1.0000

1.0000

1.0000

1.0000

 

 

 

 

 

 

 

 

 

106.25%

1.0062

1.0392

1.0328

1.0102

1.0070

1.0057

0.9878

1.0105

 

 

 

 

 

 

 

 

 

112.50%

1.0109

1.0733

1.0617

1.0211

1.0130

1.0112

0.9800

1.0194

118.75%

1.0141

1.1001

1.0848

1.0329

1.0180

1.0163

0.9705

1.0284

 

 

 

 

 

 

 

 

 

125%

1.0159

1.1174

1.0999

1.0455

1.0220

1.0211

0.9614

1.0368

 

 

 

 

 

 

 

 

 

130%

1.0161

1.1229

1.1050

1.0562

1.0244

1.0247

0.9554

1.0430

Black area denotes where operation is not recommended.

ECM Fan Motor

Airflow

 

 

Cooling

 

 

 

Heating

 

% of

Total

Sensible

S/T

Power

Heat of

Heating

Power

Heat of

Rated

Capacity

Capacity

Rejection

Capacity

Extraction

 

 

 

68.75%

0.9470

0.8265

0.8727

0.9363

0.9449

 

 

 

 

 

 

 

 

 

 

 

 

75%

0.9619

0.8593

0.8933

0.9455

0.9587

0.9700

1.0822

0.9410

 

 

 

 

 

 

 

 

 

81.25%

0.9747

0.8943

0.9175

0.9564

0.9711

0.9775

1.0536

0.9579

 

 

 

 

 

 

 

 

 

87.50%

0.9853

0.9302

0.9441

0.9691

0.9821

0.9851

1.0304

0.9733

93.75%

0.9938

0.9659

0.9719

0.9837

0.9918

0.9925

1.0125

0.9874

 

 

 

 

 

 

 

 

 

100%

1.0000

1.0000

1.0000

1.0000

1.0000

1.0000

1.0000

1.0000

 

 

 

 

 

 

 

 

 

106.25%

1.0041

1.0313

1.0271

1.0181

1.0069

1.0074

0.9928

1.0112

112.50%

1.0060

1.0584

1.0522

1.0381

1.0123

1.0148

0.9909

1.0210

 

 

 

 

 

 

 

 

 

118.75%

1.0070

1.0815

1.0740

1.0598

1.0174

1.0222

0.9622

1.0377

 

 

 

 

 

 

 

 

 

125%

1.0076

1.0998

1.0916

1.0834

1.0225

1.0295

0.8681

1.0712

130%

1.0083

1.1110

1.1018

1.1035

1.0271

1.0354

0.8456

1.0844

Black area denotes where operation is not recommended.