GT-PG (50YE) Series
PSC Blower Performance Data
Airflow in CFM with wet coil and clean air filter
Model | Fan | Rated | Min |
|
|
|
| Airflow (cfm) at External Static Pressure (in. wg) |
|
|
|
| ||||||||
Speed | Airflow | CFM | 0.00 | 0.05 | 0.10 | 0.15 | 0.20 | 0.25 | 0.30 | 0.35 | 0.40 | 0.45 | 0.50 | 0.60 | 0.70 | 0.80 | 0.90 | 1.00 | ||
| ||||||||||||||||||||
| HI | 600 | 450 | 704 | 708 | 711 | 702 | 693 | 692 | 690 | 683 | 675 | 658 | 640 | 598 | 515 |
|
|
| |
018 | MED | 600 | 450 | 602 | 601 | 599 | 590 | 581 | 583 | 585 | 579 | 573 | 560 | 547 | 492 |
|
|
|
| |
| LOW | 600 | 450 | 531 | 529 | 527 | 522 | 517 | 512 | 506 | 501 | 495 | 479 | 462 |
|
|
|
|
| |
| HI | 850 | 600 | 965 | 960 | 954 | 943 | 931 | 923 | 914 | 898 | 882 | 862 | 842 | 794 | 725 | 635 |
|
| |
024 | MED | 850 | 600 | 841 | 833 | 825 | 817 | 809 | 800 | 790 | 777 | 763 | 747 | 731 | 686 | 623 |
|
|
| |
| LOW | 850 | 600 | 723 | 715 | 707 | 703 | 698 | 689 | 680 | 668 | 656 | 642 | 627 |
|
|
|
|
| |
| HI | 950 | 750 | 1271 | 1250 | 1229 | 1207 | 1185 | 1164 | 1143 | 1118 | 1093 | 1061 | 1029 | 953 | 875 | 753 |
|
| |
030 | MED | 950 | 750 | 1048 | 1037 | 1025 | 1016 | 1007 | 994 | 981 | 962 | 943 | 915 | 886 | 822 |
|
|
|
| |
| LOW | 950 | 750 | 890 | 887 | 884 | 879 | 874 | 865 | 855 | 842 | 829 | 809 | 789 |
|
|
|
|
| |
| HI | 1250 | 900 | 1411 | 1407 | 1402 | 1390 | 1378 | 1370 | 1361 | 1326 | 1290 | 1248 | 1205 | 1083 | 942 |
|
|
| |
036 | MED | 1250 | 900 | 1171 | 1164 | 1156 | 1145 | 1133 | 1113 | 1092 | 1064 | 1035 | 997 | 958 |
|
|
|
|
| |
| LOW | 1250 | 900 | 983 | 967 | 950 | 943 | 936 | 936 |
|
|
|
|
|
|
|
|
|
| |
| HI | 1400 | 1050 | 1634 | 1626 | 1618 | 1606 | 1594 | 1583 | 1571 | 1539 | 1507 | 1464 | 1420 | 1265 | 1078 |
|
|
| |
042 | MED | 1400 | 1050 | 1332 | 1323 | 1314 | 1298 | 1282 | 1263 | 1243 | 1206 | 1169 | 1115 | 1060 |
|
|
|
|
| |
| LOW | 1400 | 1050 | 1130 | 1109 | 1088 | 1086 | 1084 | 1066 | 1048 | 1052 | 1055 |
|
|
|
|
|
|
| |
| HI | 1600 | 1200 | 1798 | 1781 | 1764 | 1738 | 1711 | 1688 | 1665 | 1630 | 1595 | 1555 | 1514 | 1420 | 1239 |
|
|
| |
048 | MED | 1600 | 1200 | 1384 | 1382 | 1379 | 1375 | 1371 | 1356 | 1341 | 1318 | 1294 | 1261 | 1227 |
|
|
|
|
| |
| LOW | 1600 | 1200 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| HI | 1950 | 1500 | 2311 | 2306 | 2300 | 2290 | 2279 | 2268 | 2257 | 2233 | 2209 | 2175 | 2140 | 2088 | 1990 | 1901 | 1856 | 1752 | |
060 | MED | 1950 | 1500 | 2058 | 2049 | 2039 | 2028 | 2016 | 2000 | 1983 | 1966 | 1949 | 1935 | 1920 | 1874 | 1807 | 1750 | 1670 | 1582 | |
| LOW | 1950 | 1500 | 1868 | 1863 | 1858 | 1858 | 1858 | 1848 | 1838 | 1822 | 1806 | 1799 | 1792 | 1749 | 1699 | 1636 | 1570 |
|
Black areas denote ESP where operation is not recommended.
Units factory shipped on medium speed. Other speeds require field selection.
All airflow is rated and shown above at the lower voltage if unit is dual voltage rated, e.g. 208V for
Bryant: Whatever it Takes. | ||