Bryant GT-PG (50YE) manual Entering Air Correction Factors, Air DBF, Air WBF

Models: GT-PG (50YE)

1 48
Download 48 pages 63.8 Kb
Page 11
Image 11

Bryant Geothermal Heat Pump Systems

Entering Air Correction Factors

 

Heating

 

 

 

 

 

Entering

Heating

Power

Heat of

Air DB°F

Capacity

Extraction

 

45

1.0514

0.7749

1.1240

 

 

 

 

50

1.0426

0.8113

1.1032

 

 

 

 

55

1.0329

0.8525

1.0802

 

 

 

 

60

1.0224

0.8980

1.0551

65

1.0114

0.9473

1.0282

 

 

 

 

68

1.0046

0.9786

1.0115

 

 

 

 

70

1.0000

1.0000

1.0000

75

0.9883

1.0556

0.9706

 

 

 

 

80

0.9764

1.1135

0.9404

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering

Total

 

 

Sensible Cooling Capacity Multiplier -

 

 

 

Heat of

 

 

 

Entering DB °F

 

 

 

Power

Air WB°F

Capacity

 

 

 

 

 

 

 

 

 

 

Rejection

60

65

70

75

80

80.6

85

90

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

0.7432

0.9111

*

*

*

*

*

*

*

*

0.9866

0.7901

55

0.8202

0.7709

0.8820

1.0192

*

*

*

*

*

*

0.9887

0.8527

60

0.8960

 

0.6702

0.8540

1.0473

*

*

*

*

*

0.9924

0.9146

 

 

 

 

 

 

 

 

 

 

 

 

 

65

0.9705

 

 

0.6491

0.8657

1.0809

1.1066

*

*

*

0.9975

0.9757

 

 

 

 

 

 

 

 

 

 

 

 

 

66.2

0.9882

 

 

0.5939

0.8152

1.0333

1.0592

1.2481

*

*

0.9990

0.9903

67

1.0000

 

 

0.5559

0.7801

1.0000

1.0261

1.2158

*

*

1.0000

1.0000

 

 

 

 

 

 

 

 

 

 

 

 

 

70

1.0438

 

 

 

0.6377

0.8645

0.8913

1.0847

1.2983

*

1.0042

1.0362

 

 

 

 

 

 

 

 

 

 

 

 

 

75

1.1159

 

 

 

 

0.6008

0.6289

0.8323

1.0578

1.2773

1.0123

1.0959

* = Sensible capacity equals total capacity

AHRI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling - 80.6°F DB/66.2°F WB, 1 and Heating - 68°F DB/59°F WB entering air temperature