TABLE 14.3: SOFT LOCKOUT CODES DISPLAYED

B.Trouble shooting problems where a soft lockout code is displayed. When a soft lockout occurs, the boiler will shut down and the display will alternate between the number “9” and the letter “b” followed by a two digit service code. The boiler will automatically restart once the condition that caused the lockout is corrected.

TABLE 14.3: SOFT LOCKOUT CODES DISPLAYED

CODE

CONDITION

POSSIBLE CAUSES

 

 

• Blockage in intake or vent system.

 

 

• Vent and/or intake system not constructed in accordance with Part VI.

b 08

Pressure switch circuit open

• Blocked or leaking pressure switch tubing

• Heat exchanger or burner blockage

 

 

 

 

• Terminals exposed to high winds

 

 

• Blockage in condensate trap above vent.

 

 

 

 

 

• Heating load at time of error was far below the minimum firing rate of the

 

MCBA supply sensor detected temperatures in excess

boiler

b 18

• Defective primary pump or no flow in primary loop (Piping Method 1)

of 200°F

 

• Control system miswired so that boiler operation is permitted when no

 

 

 

 

zones are calling

 

 

 

b 19

MCBA return sensor detected temperatures in excess

• See possible causes for “b18”

of 200°F

• Flow through boiler reversed

 

 

 

• Sensor wiring reversed

 

 

 

 

 

• Flow through boiler reversed. Verify correct piping and pump orientation.

 

MCBA is reading a return sensor temperature higher

• No boiler water flow. Verify that system is purged of air and that

b 24

than the supply sensor temperature. Condition must be

appropriate valves are open.

 

present for at least 75s for this error code to appear.

• Sensor wiring reversed.

 

 

• Supply or return sensor defective.

 

 

 

 

 

• See possible causes for “b18”

b 25

Supply water temperature has risen too quickly

• Inadequate boiler water flow. Verify that pump is operating and that pump

 

 

and piping are sized per Part VIII of this manual

 

 

 

b 26

Boiler safety limit, or external limit wired across

• See possible causes for “b18”

terminals 3&4, is open.

• Defective supply sensor.

 

 

 

 

b 30

Temperature rise between supply and return is too high.

• Inadequate boiler water flow. Verify that pump is operating and that pump

and piping are sized per Part VIII of this manual

 

 

 

 

 

 

 

• Blockage in pressure switch hose

 

 

• Pressure switch wires shorted together

b 61

Pressure switch circuit closed with fan off

• Defective pressure switch

 

 

• Loose or miswired fan speed harness (if “b61” error code is observed

 

 

while fan is running)

 

 

 

b 65

Fan is not achieving set point speed

• Loose or incorrect fan speed control connection

• Defective fan

 

 

 

 

 

61

Page 61
Image 61
Burnham 101008-01R1-2/07 manual 3 SOFT LOCKOUT CODES DISPLAYED, Code, Condition, Possible Causes