Figure 36: Minimum Piping Requirements for V9A Tankless Heater Manifolds
Table IV: Tankless Heater Ratings |
|
| |||
|
|
|
|
| |
Boiler | Number of | ||||
Model | 1 | 2 |
| 3 | 4 |
|
| ||||
V903A | 6.75 |
| |||
V904A | 7.5 |
| |||
V905A | 7.5 |
| |||
V905A | 7.5 |
| |||
V906A | 7.5 | 15 |
| ||
V908A | 7.5 | 15 |
| ||
V909A | 7.5 | 15 |
| 22.5 | |
V910A | 7.5 | 15 |
| 22.5 | |
V911A | 7.5 | 15 |
| 22.5 | |
V912A | 7.5 | 15 |
| 22.5 | 30 |
Figure 37a: Schematic Tankless Heater Piping | Notes: |
|
1. Ratings are given in gallons per minute continuous flow of water heated from 40°F to 140°F with 200°F boiler water.
2. For tankless heater quantities less than maximum allowable, it is important that water heaters be centrally located in the boiler.
See Figure 8 for appropriate locations.
3. Tankless heater pressure drop is 5.5 PSI at
7.5 GPM.
41