Installation Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
Step 1 — Rig and Place the Unit. . . . . . . . . . . . . . . . . . 1
•RIGGING
•PLACING UNIT
•MOUNTING UNIT
Step 2 — Check Compressor Mounting . . . . . . . . . . 3
Step 3 — Cooler Fluid and Drain Piping
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
•PREPARATION FOR
•PREPARATION FOR WINTER SHUTDOWN
Step 4 — Make Electrical Connections . . . . . . . . . . . 7
•POWER SUPPLY
•POWER WIRING
Step 5 — Install Accessories . . . . . . . . . . . . . . . . . . . . 11
•ELECTRICAL
•HOT GAS BYPASS
Step 6 — Refrigerant Circuit. . . . . . . . . . . . . . . . . . . . . 11
•LEAK TESTING
•DEHYDRATION
•REFRIGERANT CHARGE
SAFETY CONSIDERATIONS
Installing, starting up, and servicing
Only trained, qualified installers and service mechanics should install, start up, and service this equipment (Fig. 1).
Untrained personnel can perform basic maintenance func- tions such as cleaning coils. All other operations should be per- formed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
•Follow all safety codes.
•Wear safety glasses and work gloves.
•Keep quenching cloth and fire extinguisher nearby when brazing.
•Use care in handling, rigging, and setting bulky equipment.
•See Tables 1A and 1B for Physical Data.
ELECTRIC SHOCK HAZARD
Open all remote disconnects before servicing this equipment.
Fig. 1 — Model 30GTN (020 Shown)
INSTALLATION
Step 1 — Rig and Place the Unit
RIGGING — Preferred method is with spreader bars from above the unit. Use
If overhead rigging is not possible, place chiller on skid or pad for rolling or dragging. When rolling, use a minimum of 3 rollers. When dragging, pull the pad. Do not apply force to the unit. When in final position, raise from above to lift unit off pad.
All panels must be in place when rigging.
PLACING UNIT — There must be at least 4 ft (1.2 m) for service and for unrestricted airflow on all sides of unit, and a minimum of 8 ft (2.4 m) clear air space above unit. Provide ample room for servicing cooler. For cooler removal see clear- ance requirements in Fig.
If unit is to be used in an area with high solar radiation, mounted position should be such that control box is not ex- posed to direct solar radiation. Exposure to direct solar radia- tion could affect the temperature switch controlling cooler heaters. See Table 2.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book | 2 | PC 903 | Catalog No. | Printed in U.S.A. | Form | Pg 1 | Replaces: New | |