Step 5 — Install Accessories
ELECTRICAL — A number of electrical accessories are available to provide the following optional features (for details, refer to the Controls,
•Energy Management Module (used for any of the fol- lowing types of temperature reset, demand limit and ice features):
—4 to 20 mA leaving fluid temperature reset (requires
—4 to 20 mA cooling set point reset (requires field- supplied 4 to 20 mA generator)
—Discrete inputs for
—4 to 20 mA demand limit (requires
—Discrete input for Ice Done switch (requires field- supplied dry contacts)
•Chilled fluid flow switch/interlock
•Navigator display:
Provides
HOT GAS BYPASS — Hot gas bypass usually is not rec- ommended because it results in application of equipment out of its normal design application range. However, if its use is required, the appropriate hot gas bypass package may be used. For installation details, refer to separate instructions supplied with the accessory package.
Step 6 — Refrigerant Circuit
LEAK TESTING — Units are shipped with complete op- erating charge of
DEHYDRATION — Refer to Carrier Standard Service Tech- niques Manual, Chapter 1, Refrigerants, Sections 6 and 7 for details. Do not use compressor to evacuate system.
REFRIGERANT CHARGE (Refer to Table 1A or 1B) — Immediately ahead of filter drier in each circuit is a factory- installed liquid line service valve. Each valve has a