Carrier 30GTN015-035 installation instructions Rigging with Spreader Bars Field Supplied

Models: 30GTN015-035

1 12
Download 12 pages 52.18 Kb
Page 3
Image 3
Fig. 2 — Rigging with Spreader Bars

 

MAXIMUM

LIFTING

CENTER OF GRAVITY

 

 

UNIT

SHIP WT

HOLES

“B”

“C”

“D”

30GTN

“A”

 

 

 

 

 

 

 

 

 

 

 

Lb

Kg

in.

mm

in.

mm

in.

mm

in.

mm

015

1876

851

94.0

2388

48.0

1219

23.0

583

49.5

1256

020

2031

921

94.0

2388

47.5

1207

23.0

583

49.5

1256

025

2415

1095

94.0

2388

51.0

1295

34.5

876

73.5

1867

030

2606

1182

94.0

2388

51.0

1295

34.5

876

73.5

1867

035

3365

1526

127.0

3225

66.5

1689

35.5

901

73.5

1867

Fig. 2 — Rigging with Spreader Bars

(Field Supplied)

Table 2 — Temperature Limits for Standard Units

TEMPERATURE

F

C

Maximum Ambient Temperature

125

52

Minimum Ambient Temperature

0

–18

Maximum Cooler EWT*

95

35

Maximum Cooler LWT

70

21

Minimum cooler LWT†

38

3.3

LEGEND

 

 

EWT — Entering Fluid (Water) Temperature

LWT — Leaving Fluid (Water) Temperature

*For sustained operation, EWT should not exceed 85 F (29.4 C). †Unit requires modification below this temperature.

MOUNTING UNIT — When unit is in proper location, use of mounting holes in base rails is recommended for securing unit to supporting structure, or for mounting unit on vibration isolators if required. See Fig. 3-5. Fasteners for mounting unit

are field supplied. Be sure unit is level to ensure proper oil return to compressor.

Step 2 — Check Compressor Mounting — As shipped, compressor is held down by 4 bolts. After unit is in- stalled, loosen each bolt using nut indicated in Fig. 6 until the flat washer (3/8 in.) can be moved with finger pressure.

Step 3 — Cooler Fluid and Drain Piping Con- nections — When facing the cooler side of the unit, the re- turn water connection is on the left and the leaving water con- nection is on the right. See Fig. 3-5 and 7. Install a minimum 40-mesh strainer in the cooler fluid inlet line just ahead of and as close as possible to the cooler. Provide a means of venting air from the high point of the field-installed piping.

After field piping is complete, freeze-up protection is rec- ommended using inhibited ethylene glycol or other suitable in- hibited antifreeze solution and electric heat tapes in area where piping is exposed to low ambient temperatures (34 F [1 C] or below). Heat tapes should possess a rating for area ambients and be covered with a suitable thickness of closed-cell insulation. Route power for heating tapes from a separately- fused disconnect. Identify disconnect as heat tape power source with a warning that power must not be turned off except when unit is being serviced.

The cooler drain connection is at the opposite end from the compressor (See Fig. 3-5). Insulate the drain piping (in the same manner as the chilled water piping) for at least one ft (305 mm) from cooler.

PREPARATION FOR YEAR-ROUND OPERATION — If unit is on year-round operation, add sufficient inhibited ethyl- ene glycol or other suitable inhibited antifreeze solution to chilled water to prevent freezing under low-ambient operating conditions. Consult local water authority on characteristics of area water and add a recommended inhibitor to the chilled water.

PREPARATION FOR WINTER SHUTDOWN — Do not shut off control power disconnect during off-season shutdown. At end of cooling season:

1.Drain water from system.

2.Replace drain plug and put 2 gallons (8 liters) of inhib- ited ethylene glycol (or other suitable inhibited anti- freeze) in cooler to prevent freezing of residual water. (Remove plug on top of leaving chilled water nozzle to add liquid.)

3.At the beginning of the next cooling season, refill cooler and add recommended inhibitor.

3

Page 3
Image 3
Carrier 30GTN015-035 Rigging with Spreader Bars Field Supplied, Temperature Limits for Standard Units