Carrier 30GTN015-035 installation instructions

Models: 30GTN015-035

1 12
Download 12 pages 52.18 Kb
Page 9
Image 9
Manual background

Table 3B — Electrical Data — Unit with Factory-Installed Motormaster® I Control

UNIT

 

 

 

UNIT

 

 

 

 

CONTROL CIRCUIT

 

SIZE

Voltage

Supplied*

MCA

MOCP

ICF

Rec Fuse

V-Hz

 

Supplied

 

MCA and

30GTN

V-Hz (3 Ph)

Min

Max

Size

(Single Ph)

 

Min

Max

 

MOCP

 

 

 

 

 

 

208/230-60

187

253

82.2

125

278.4

100

115-60

 

104

127

 

30

 

460-60

414

506

38.3

60

129.3

45

115-60

 

104

127

 

30

015

575-60

518

633

30.8

50

105.6

40

115-60

 

104

127

 

30

 

380-60

418

342

43.9

70

152.8

60

230-60

 

198

254

 

15

 

380/415-50

342

440

51.9

80

181.5

70

230-50

 

198

254

 

15

 

208/230-60

187

253

97.4

150

357.4

125

115-60

 

104

127

 

30

 

460-60

414

506

49.6

80

182.3

60

115-60

 

104

127

 

30

020

575-60

518

633

42.0

70

129.6

50

115-60

 

104

127

 

30

 

380-60

418

342

51.1

80

198.8

60

230-60

 

198

254

 

15

 

380/415-50

342

440

63.0

100

231.5

80

230-50

 

198

254

 

15

 

208/230-60

187

253

124.7

200

458.4

150

115-60

 

104

127

 

30

 

460-60

414

506

60.7

100

232.3

80

115-60

 

104

127

 

30

025

575-60

518

633

51.5

80

173.6

70

115-60

 

104

127

 

30

 

380-60

418

342

64.7

110

254.8

80

230-60

 

198

254

 

15

 

380/415-50

342

440

71.0

110

261.5

90

230-50

 

198

254

 

15

 

208/230-60

187

253

145.5

250

518.4

175

115-60

 

104

127

 

30

 

460-60

414

506

68.7

110

262.3

90

115-60

 

104

127

 

30

030

575-60

518

633

54.0

90

185.6

70

115-60

 

104

127

 

30

 

380-60

418

342

73.6

125

287.8

90

230-60

 

198

254

 

15

 

380/415-50

342

440

90.3

150

353.5

110

230-50

 

198

254

 

15

 

208/230-60

187

253

203.0

350

708.6

250

115-60

 

104

127

 

30

035

460-60

414

506

91.1

150

357.4

110

115-60

 

104

127

 

30

575-60

518

633

80.7

125

289.0

100

115-60

 

104

127

 

30

 

 

 

 

380-60

418

342

111.1

175

393.7

150

230-60

 

198

254

 

15

LEGEND

ICF — Maximum Instantaneous Current Flow during starting (the point in the starting sequence where the sum of the LRA for the starting compressor, plus the total RLA for all running compressors, plus the total FLA for all running fan motors is maximum).

MCA — Minimum Circuit Amps (complies with National Elec- trical Code [NEC, U.S.A.], Section 430-24)

MOCP — Maximum Overcurrent Protection

*Units are suitable for use on electrical systems where voltage sup- plied to unit terminals is not below or above listed minimum and maximum limits.

NOTE: Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent voltage imbalance.

Percent Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Determine maximum deviation from average voltage:

(AB) 243 – 239 = 4 v (BC) 239 – 236 = 3 v (AC) 239 – 238 = 1 v

Maximum deviation is 4 v. Determine percent voltage imbalance:

4

% Voltage Imbalance = 100 x

239

= 1.7%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: Contact your local electric utility company immediately if the supply voltage phase imbalance is more than 2%.

Example: Supply voltage is 240-3-60.

AB = 243 v

BC = 236 v

AC = 238 v

243 + 236 + 238

Average voltage =

3

=239 v

9

Page 9
Image 9
Carrier 30GTN015-035 installation instructions