Carrier 33PILOT-01 owner manual Time Schedule Screen

Models: 33PILOT-01

1 8
Download 8 pages 21 Kb
Page 5
Image 5
Fig. 11 — Time Schedule Screen

CONFIG AND SETPOINT TABLES — If the CONFIG or SETPOINTS table option is selected from the Program screen, and if there is more than one entry in the corresponding table list, then the System Pilot displays a Table List screen. If there is only a single table, the System Pilot displays the contents of the table.

Only two types of configuration tables will be available in Security Level 2, Holiday Configuration tables and Occupancy tables (if attached to a device with an occupancy schedule).

NOTE: The CONFIG function is not available if the System Pilot is set to Security Levels 3 or 4. The SETPOINTS func- tion is not available if the system is set to Security level 3.

The top line of the Table List screen shows the table type that was selected. The bottom line shows text and error mes- sages, as applicable. The center portion of the screen shows the table list. This consists of the table names from the specified list, arranged in alphabetical order.

Use the SCROLL UP/DOWN buttons or the NAVIGATE knob to scroll through the list. Press the SELECT button to display the highlighted line.

If a table type with multiple table entries was selected, the System Pilot will display a Multiple Table List screen with all of the table names associated with that table type.

If it is a table type with a single table entry, the System Pilot will display a Standard Table screen.

Multiple Table List Screen — If multiple tables of a selected type are available, or if SCHEDULE is selected from the Pro- gram screen and there are multiple schedules, the System Pilot will display a Multiple Table List screen with all of the table names associated with that table type.

The top line shows the name of the table that was selected. The bottom line shows text and error messages, as applicable. The center portion of the screen lists the associated tables in alphabetical order. If the list has more than 7 tables, then the first 7 tables will be displayed.

Use the SCROLL UP/DOWN buttons or the NAVIGATE knob to scroll through the list. If there are more than 7 tables, pressing PAGE UP/DOWN will display the previous or next 7 names from the list. Press the SELECT button to read the highlighted table from the attached device and display an appropriate screen. A Time Schedule screen is displayed if the table is a time schedule, or a Standard Table screen is displayed for any other table. Pressing the EXIT button causes the System Pilot to return to the Table List screen.

Standard Table Screen — If a table type with a single table en- try is selected from a Table List screen, or a table (other than a schedule) is selected from a Multiple Table List screen, the System Pilot displays a Standard Table screen.

The top line shows the 8-character table name. The center portion of the screen shows the table data.

Configuration and set point data is read from the attached device once, when the table is first selected and displayed. There will be one point/decision per line. If there are more than seven decisions/points, the first seven will be displayed. The bottom line displays text and error messages, as applicable.

Use the SCROLL UP/DOWN buttons or the NAVIGATE knob to scroll through the data. If there are more than 7 deci- sions/points, pressing PAGE UP/DOWN will display the previous or next 7 decisions/points. As the user scrolls through the table, the System Pilot will highlight the current decision/ point and if there is an associated point name, the 24-character descriptor will be displayed on the bottom line. If there is no associated point name, the System Pilot will display the 24-character descriptor in the center portion of the screen.

If the SELECT button is pressed and the current point is ed- itable, the System Pilot allows the user to modify the point.

If the EXIT button is pressed, the System Pilot exits to the next higher screen.

SCHEDULE — Selecting the SCHEDULE option from the Program screen and then selecting a Time Schedule table displays the Time Schedule screen as shown in Fig. 11. This example shows all 8 of the time schedule periods, even though only the first 6 (plus the header line) will actually be shown on the System Pilot when this screen is entered.

NOTE: This function is not available if the System Pilot is set to Security Levels 3 or 4.

The top line shows the 8-character schedule name. The bottom line displays text and error messages, if applicable. The center portion of the screen shows the schedule data which are the occupied and unoccupied times for each period and the days to which the period applies. The time is displayed with a 24-hour clock with colon (00:00 to 24:00). The day flags are displayed as 8 bits (0 or 1), for Monday through Sunday plus holiday. The times and day flags are modifiable. The period numbers and the header line are fixed. Each of the day flags is treated as a separate field, therefore, there are 12 modifiable fields per line.

Use the SCROLL UP/DOWN buttons or the NAVIGATE knob to scroll through the table one line at a time. If the SELECT button is pressed, the System Pilot allows the user to modify the data on the current line (starting with Occupied hour). Use the NAVIGATE knob to move within the line. As each field is highlighted, the truncated 24-character descriptor is displayed on the message line. Use the INC/DEC buttons or the MODIFY rotary knob to adjust the highlighted value. If the EXIT button is pressed, the System Pilot will return to the Program screen or the Multiple Table List screen.

DETACH — Select this option from the Program screen to disconnect from the device to which the System Pilot is currently attached. The System Pilot will attach to itself and display the System Pilot default screen.

Modifying Set Points — The VVT® zone controller default screen displays two set points. The Remote Attach Default screen will display up to two set points. The user can modify the displayed set points by turning the MODIFY rotary knob or pressing the INC/DEC buttons. The displayed set points will blink.

NOTE: This function is not available if the System Pilot is set to security level 4.

The System Pilot will modify a set point subject to the limits read from the controller. If there are two set points, the System Pilot will modify them simultaneously and will preserve the difference between them subject to the limits read from the controller.

The System Pilot has configurable high and low limits for set points, as defined in the System Pilot Configuration Table and the System Pilot remote attach configuration table. On a Remote Attach Default screen, the limits will be applicable to

 

Fig. 11 — Time Schedule Screen

5

606

 

Page 5
Image 5
Carrier 33PILOT-01 owner manual Time Schedule Screen

FAQ

How do I access the CONFIG and SETPOINTS tables?

Select the option from the Program screen. The System Pilot will display the tables, allowing you to choose the desired one.

What tables are available in Security Level 2?

In Security Level 2, you can access Holiday Configuration tables and Occupancy tables if attached to a device with an occupancy schedule.

Can I modify the set points for my air conditioner?

Yes, you can modify the displayed set points using the MODIFY rotary knob or INC/DEC buttons.