Carrier 33PILOT-01 owner manual Holiday HOLDYxxS Configuration Table, 3V Bus Scan Screen

Models: 33PILOT-01

1 8
Download 8 pages 21 Kb
Page 7
Image 7
Fig. 13 — 3V™ Bus Scan Screen

Fig. 13 — 3V™ Bus Scan Screen

Pressing the EXIT button causes the System Pilot to return to the Master Zone Controller (Linkage Coordinator) Default screen.

Holiday (HOLDYxxS) Configuration Table —

The Holiday Configuration Table is shown in Table 1. The Sys- tem Pilot has 30 configurable Holiday tables (HOLDY01S – HOLDY30S). An explanation of each configuration decision follows.

7

START MONTH — Use this decision to indicate the month of the year in which the holiday will begin.

Start Month:

Allowable Entries 1 to 12

 

Default Value

1

START DAY — Use this decision to indicate the day of the month on which the holiday will begin.

Start Day:

Allowable Entries 1 to 31

 

Default Value

1

DURATION — Use this decision to indicate the number of consecutive days that the holiday will last. If you enter 0 in this decision, the holiday schedule will be disabled.

Duration:

Allowable Entries 0 = Disable or 1 to 365

 

Default Value

0

 

 

Table 1 — Holiday Configuration (HOLDYXXS)

 

 

 

 

 

DESCRIPTION

DISPLAY

POINT

RANGE

DEFAULT

Start Month

XX

MONTH

 

1-12

1

Start Day

XX

DAY

 

1-31

1

Duration

XXX

DURATION

0-365

0

Page 7
Image 7
Carrier 33PILOT-01 owner manual Holiday HOLDYxxS Configuration Table, 3V Bus Scan Screen, Holiday Configuration HOLDYXXS

FAQ

What is the purpose of the Holiday Configuration Table?

The Holiday Configuration Table allows for the configuration of 30 different holiday tables for the Carrier 33PILOT-01 Air Conditioner.

How can I disable the holiday schedule?

You can enter 0 in the duration decision to disable the holiday schedule.

How do I return to the Master Zone Controller Linkage Coordinator Default screen?

Press the EXIT button while using the Fig.133V Bus Scan Screen to return to the Master Zone Controller Linkage Coordinator Default screen.