Fig. 13 — 3V™ Bus Scan Screen
Pressing the EXIT button causes the System Pilot to return to the Master Zone Controller (Linkage Coordinator) Default screen.
Holiday (HOLDYxxS) Configuration Table —
The Holiday Configuration Table is shown in Table 1. The Sys- tem Pilot has 30 configurable Holiday tables (HOLDY01S – HOLDY30S). An explanation of each configuration decision follows.
7
START MONTH — Use this decision to indicate the month of the year in which the holiday will begin.
Start Month: | Allowable Entries 1 to 12 | |
| Default Value | 1 |
START DAY — Use this decision to indicate the day of the month on which the holiday will begin.
Start Day: | Allowable Entries 1 to 31 | |
| Default Value | 1 |
DURATION — Use this decision to indicate the number of consecutive days that the holiday will last. If you enter 0 in this decision, the holiday schedule will be disabled.
Duration: | Allowable Entries 0 = Disable or 1 to 365 | ||||
| Default Value | 0 |
|
| |
Table 1 — Holiday Configuration (HOLDYXXS) | |||||
|
|
|
|
| |
DESCRIPTION | DISPLAY | POINT | RANGE | DEFAULT | |
Start Month | XX | MONTH |
| 1 | |
Start Day | XX | DAY |
| 1 | |
Duration | XXX | DURATION | 0 |