Carrier 38AUQ appendix Defrost, Reversing valve control, Compressor control

Models: 38AUQ

1 36
Download 36 pages 12.25 Kb
Page 23
Image 23
Defrost

Fig. 21 — Defrost Control Board (DFB) Location

Defrost

The defrost control mode is a time/temperature sequence. There are two time components: The continuous run period and the test/defrost cycle period. The temperature component is provided by the defrost thermostat (DFT1) mounted on the outdoor coil.

The continuous run period is a fixed time period between the end of the last defrost cycle (or start of the current Heating cy- cle) during which no defrost will be permitted. This period can be set at 30, 60, 90 or 120 minutes by changing the positions of DIP switches SW1 and SW2 (see Fig. 23 and Table 13). The default run period is 60 minutes.

DIP

Switches

Reversing valve controlSpeed-Up

Jumpers

Fig. 22 — Defrost Control Board (DFB) Arrangement

Fig. 23 — DIP Switch Settings — Defrost Board

Reversing valve control

The DFB has two outputs for unit reversing valve control. Op- eration of the reversing valves is based on internal logic; this application does not use an “O” or “B” signal to determine re- versing valve position. Reversing valves are energized during the Cooling stages and de-energized during Heating cycles. Once energized at the start of a Cooling stage, the reversing valve will remain energized until the next Heating cycle de- mand is received. Once de-energized at the start of a Heating cycle, the reversing valves will remain de-energized until the next Cooling stage is initiated.

Compressor control

The DFB receives inputs indicating Stage 1 Cooling and Stage 1 Heating from the space thermostat or unit control system (PremierLink); it generates commands to start compressors with or without reversing valve operation to produce Stage 1 Cooling (one compressor), or Stage 1 Heating (both compres- sors run).

At the end of the continuous run period, the defrost control will test for a need to defrost. On unit sizes 04-07 (single compres- sor designs), DFT1 controls the start and termination of the de- frost cycle. If DFT1 is still open, the defrost test/run window is closed and the control repeats the continuous run period. If DFT1 is closed, the defrost cycle is initiated. The defrost period will end when DFT1 opens (indicating the outdoor coil has been cleared of frost and ice) or a 10 minute elapsed period ex- pires, whichever comes first.

At the end of the unit defrost cycle, the unit will be returned to Heating cycle for a full continuous run period.

If the space heating load is satisfied and compressor operation is terminated, the defrost control will remember where the run period was interrupted. On restart in Heating, the defrost con- trol will resume unit operation at the point in the run period where it was last operating.

Table 13 —Dip Switch Position

Switch No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

 

1

2

 

 

1

2

 

 

1

2

 

 

3

 

 

1

 

 

 

1

 

 

 

1

 

 

 

1

 

 

 

1

 

 

On

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

0

 

 

 

 

0

 

 

 

0

 

 

 

 

 

0

 

 

Off

 

 

30 minutes

 

 

 

60 minutes

 

 

 

90 minutes

 

 

 

120 minutes

 

 

 

Fan Delay

 

 

23

Page 23
Image 23
Carrier 38AUQ appendix Defrost, Reversing valve control, Compressor control