Carrier Electrical Data — 38AUQ*07-12, Hz Units, Full Load Amps, Locked Rotor Amps, Protection

Models: 38AUQ

1 36
Download 36 pages 12.25 Kb
Page 14
Image 14
Table 8 — Electrical Data — 38AUQ*07-12

 

Table 8 — Electrical Data — 38AUQ*07-12

60 Hz Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

FACTORY-

NOMINAL

VOLTAGE

COMPRESSOR

FAN MOTORS

POWER

VOLTAGE

RANGE

SUPPLY

SIZE

INSTALLED

 

 

 

 

38AUQ

OPTION

V-Ph-Hz

MIN

MAX

RLA

LRA

FLA (ea)

QTY

MCA

MOCP

 

 

 

NONE OR DISCONNECT

208/230-3-60

187

253

19.0

123

1.5

2

26.8

45

 

 

 

 

 

CONVENIENCE OUTLET

31.6

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*07

NONE OR DISCONNECT

460-3-60

414

506

9.7

62

0.9

2

13.9

20

 

 

 

CONVENIENCE OUTLET

16.1

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE OR DISCONNECT

575-3-60

518

633

7.4

50

0.6

2

10.5

15

 

 

 

 

 

CONVENIENCE OUTLET

12.2

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE OR DISCONNECT

208/230-3-60

187

253

25.0

164

1.5

2

34.3

50

 

 

 

 

 

CONVENIENCE OUTLET

39.1

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*08

NONE OR DISCONNECT

460-3-60

414

506

12.2

100

0.9

2

17.1

25

 

 

 

CONVENIENCE OUTLET

19.3

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE OR DISCONNECT

575-3-60

518

633

9.0

78

0.6

2

12.5

20

 

 

 

 

 

CONVENIENCE OUTLET

14.2

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE OR DISCONNECT

208/230-3-60

187

253

30.1

225

1.5

2

40.6

60

 

 

 

 

 

CONVENIENCE OUTLET

45.4

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*12

NONE OR DISCONNECT

460-3-60

414

506

16.7

114

0.8

2

22.5

30

 

 

 

CONVENIENCE OUTLET

24.7

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE OR DISCONNECT

575-3-60

518

633

12.2

80

0.6

2

16.5

25

 

 

 

 

 

CONVENIENCE OUTLET

18.2

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

FLA

Full Load Amps

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP —

Maximum Overcurrent

 

 

Protection

NEC

National Electrical Code

RLA

Rated Load Amps

Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above the listed limits.

NOTES:

1.The MCA and MOCP values are calculated in accordance with the NEC, Article 440.

2.Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL), Standard 1995.

3.The 575-v units are UL, Canada-listed only.

4.Convenience outlet is available as a factory-installed option and is 115-v, 1 ph, 60 Hz.

5.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.

max voltage deviation from average voltage

% Voltage Imbalance = 100 x

 

 

average voltage

Example: Supply voltage is 208/230-3-60

AB = 224 v

 

 

 

BC = 231 v

 

 

 

AC = 226 v

 

 

 

(224 + 231 + 226)

681

Average Voltage =

 

 

=

 

3

3

=227

Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v

(BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v.

Determine percent of voltage imbalance.

 

4

% Voltage Imbalance

= 100 x

 

 

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

14

Page 14
Image 14
Carrier Electrical Data — 38AUQ*07-12, Hz Units, Full Load Amps, Locked Rotor Amps, Minimum Circuit Amps, Protection