CHECK VERTICAL SEPARATION — If there is any vertical separation between the indoor and outdoor units, check to ensure that the separation is within allowable limits. Relocate equipment if necessary.

Table 2 — 38AUQ*07-12 Piping Recommendations (Single-Circuit Unit)

R-410A

 

 

 

Equivalent Length

 

 

 

 

Ft

0-38

 

38-75

 

75-113

 

113-150

 

 

 

 

 

 

 

 

 

 

 

Model

Length Linear

0-25

 

25-50

 

50-75

 

75-100

 

Nominal Capacity

Length Equiiv

0-38

 

38-75

 

75-113

 

113-115

 

38AUQ*07

Liquid Line

3/8

 

3/8

 

3/8

1/2

3/8

1/2

 

Max Lift

25

 

50

 

48

75

39

100

 

Cool

 

 

 

Heat

25

 

50

 

46

60

31

60

 

Suction Line

7/8

 

7/8

 

1-1/8

 

1-1/8

 

 

Charge (lbs)

17.8

 

18.8

 

20.3

22.6

21.4

24.5

 

 

 

 

 

 

 

 

 

 

38AUQ*08

Liquid Line

1/2

 

1/2

 

1/2

 

1/2

 

 

Max Lift

25

 

50

 

75

 

100

 

 

Cool

 

 

 

 

 

Heat

25

 

50

 

60

 

60

 

 

Suction Line

7/8

1-1/8

1-1/8

 

1-1/8

 

1-1/8

 

 

Charge (lbs)

20.9

 

23.0

 

24.9

 

26.8

 

 

 

 

 

 

 

 

 

 

 

38AUQ*12

Liquid Line

1/2

 

1/2

 

1/2

 

1/2

5/8

 

Max Lift

25

 

50

 

75

 

85

100

 

Cool

 

 

 

 

Heat

25

 

50

 

60

 

60

60

 

Suction Line

7/8

1-1/8

1-1/8

 

1-1/8

 

1-1/8

1-3/8

 

Charge (lbs)

26.8

 

28.8

 

30.7

 

33.4

37.2

Legend:

 

 

 

 

 

 

 

 

 

Length Equiv

Equivalent tubing length, including effects of refrigeration specialties devices

 

 

Liquid Line

Tubing size, inches OD.

 

 

 

 

 

 

 

Max Lift

Maximum liquid lift at maximum permitted liquid line pressure drop

 

 

 

Cooling

• Indoor unit ABOVE outdoor unit

 

 

 

 

 

 

Heating

• Indoor unit BELOW outdoor unit

 

 

 

 

 

 

Suction Line

Tube size, inches OD

 

 

 

 

 

 

 

Charge

Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger

 

 

suction line size (where applicable)

 

 

 

 

 

 

 

 

NOTE:

For applications with linear length greater than 100 ft (30.5 m), contact your local Carrier representative.

CHECK VERTICAL SEPARATION — If there is any vertical separation between the indoor and outdoor units, check to ensure that the separation is within allowable limits. Relocate equipment if necessary.

PROVIDE SAFETY RELIEF — If local codes dictate an additional safety relief device, purchase locally and install locally. Installation will require the recovery of the factory shipping charge before the factory tubing can be cut and the supplemental relief device is installed.

REFRIGERANT LINE SIZING — Consider the length of the piping required between the outdoor and indoor units. The maximum allowable line length is 100 ft (30.5 m). See Table 2. Refrigerant vapor piping should be insulated.

IMPORTANT: A refrigerant receiver is not provided with the unit. Do not install a receiver.

Table 3 — Maximum Vertical Separation*

UNIT 38AUQ

UNIT 40RUQ

DISTANCE FT (M)

Unit 38AUQ

 

 

Above Unit 40RMQ

07

07

50 (15.2)

08

08

60 (18.3)

12

12

60 (18.3)

*Vertical distance between indoor and outdoor units.

INSTALL FILTER DRIER(S) AND MOISTURE INDICATOR(S) — Every unit MUST have a bi-directional filter drier in the liquid line. Locate the filter drier at the indoor unit, close to the evaporator coil’s thermal expansion valve (TXV) inlets.

38AUQ units include one Puron-duty filter drier, shipped in cartons attached to the unit basepan. Remove the filter drier and prepare to install in the liquid line at the evaporator coil. Do not remove connection fitting plugs until ready to connect and braze the filter drier into the liquid line position.

Table 4 — Puron-duty Filter Drier(s)

Model-Size

Qty

Liquid

Desiccant

Part

Line OD

Volume

Number Ref

 

 

38AUQ*07

1

3/8-in

8 cu. in.

KH43LG091

38AUQ*08

1

1/2-in

16 cu. in.

KH43LG085

38AUQ*12

1

1/2-in

16 cu. in.

KH43LG085

Installation of liquid line moisture indicating sightglass in each circuit is recommended. Locate the sightglass(es) between the outlet of the filter drier and the TXV inlet.

Refer to Table 5 for recommendations on refrigeration specialties.

Select the filter drier for maximum unit capacity and minimum pressure drop. Complete the refrigerant piping from the indoor unit to the outdoor unit before opening the liquid and suction lines at the outdoor unit.