APPENDIX A
AIR CONDITIONER AND HEAT PUMP WITH PURON® — QUICK REFERENCE GUIDE
•Puron®
•Puron® refrigerant cylinders are rose colored.
•Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
•Puron® systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating.
•Manifold sets should be 700 psig high side and 180 psig low side with 550 psig
•Use hoses with 700 psig service pressure rating.
•Leak detectors should be designed to detect HFC refirgerant.
•Puron®, as with other HFCs, is only compatible with POE oils.
•Vacuum pumps will not remove moisture from oil.
•Use only factory specified
•Do not install a
•POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
•POE oils may cause damage to certain plastics and roofing materials.
•Wrap all filter driers and service valves with wet cloth when brazing.
•A factory approved,
•Do not use an
•If indoor unit is equipped with a TXV, it must be changed to a Puron® TXV.
•Never open system to atmosphere while it is under a vacuum.
•When system must be opened for service, recover refrigerant, break vacuum with dry nitrogen before opening system.
•Always replace filter drier after opening system for service.
•Do not vent Puron® into the atmosphere.
•Do not use capillary tube coils.
•Observe all warnings, cautions, and bold text.
•All Puron® heat pumps must have indoor TXV.
•Do not leave Puron® suction line driers in place for more than 72 hours.