Step 6—Thermostatic Expansion Valve
For proper unit operation and reliability, units must be installed with
FEEDER TUBE
STUB TUBE
Due to system design, this unit must be installed with a
The outdoor section is factory equipped with a hard
Step 7—Check Defrost Thermostat
Check defrost thermostat to ensure it is properly located and securely attached. There is a liquid header with a brass distributor and feeder tube going into outdoor coil. At the end of 1 of the feeder tubes, there is a
Step 8—Make Piping Connections
Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all
DEFROST
THERMOSTAT
A97517
Fig. 7—Defrost Thermostat Location
If ANY refrigerant tubing is buried, provide a 6 in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried without further special consideration. For lengths above 36 in., consult your local distributor.
To prevent damage to unit or service valves observe the following:
•Use a brazing shield.
•Wrap service valves with wet cloth or use a heat sink material.
Outdoor units may be connected to indoor section using accessory tubing package or
SENSING BULB
DISCHARGE
MUFFLER
10 O'CLOCK
2 O'CLOCK
SENSING BULB
STRAP |
SUCTION TUBE
8 O'CLOCK | 4 O'CLOCK |
|
|
7⁄8 IN. OD & SMALLER | LARGER THAN 7⁄8 IN. OD | STRAINER | TXV |
|
| ||
| A81032 |
| A96433 |
Fig. | Fig. |
3