The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes. Failure to follow this warning can result in an electric shock, fire, or death.
CONNECT GROUND AND POWER WIRES
Connect ground wire to ground connection in control box for safety. Connect power wiring to contactor as shown in Fig.8.
Step 12—Start-Up
To prevent compressor damage or personal injury, observe the following:
•Do not overcharge system with refrigerant.
•Do not operate unit in a vacuum or at negative pressure.
•Do not disable
In scroll compressor applications:
• Dome temperatures may be hot.
DISCONNECT
PER N. E. C. AND/OR LOCAL CODES
FIELD POWER
WIRING
FIELD GROUND
WIRING
CONTACTOR
GROUND
LUG
A91056
To prevent personal injury wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following:
•Back seating service valves are not equipped with Schrader valves. Fully back seat (counter clockwise) valve stem before removing gage port cap.
Do not vent refrigerant to atmosphere. Recover during system repair or final unit disposal.
Follow these steps to properly pumpdown a system and avoid
Fig. 8—Line Power Connections
CONNECT CONTROL WIRING
Route
Use No. 18 AWG
All wiring must be NEC Class 1 and must be separated from incoming power leads.
Use furnace transformer, fan coil transformer, or accessory trans- former for control power,
NOTE: Use of available
IMPORTANT: Check factory wiring and wire connections to ensure terminations are secured properly. Check wire routing to ensure wires are not in contact with tubing, sheet metal, etc.
Step 10—Compressor Crankcase Heater
When equipped with a crankcase heater, furnish power to heater a minimum of 24 hr before starting unit. To furnish power to heater only, set thermostat to OFF and close electrical disconnect to outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than 50 ft.
Step 11—Install Electrical Accessories
Refer to the individual instructions packaged with kits or acces- sories when installing.
negative suction pressure.
1.Fully back seat (open) liquid and vapor tube service valves.
2.Unit is shipped with valve stem(s) front seated (closed) and caps installed. Replace stem caps after system is opened to refrigerant flow. Replace caps
3.Close electrical disconnects to energize system.
4.Set room thermostat to desired temperature. Be sure set point is below indoor ambient temperature.
5.Set room thermostat to HEAT or COOL and fan control to ON or AUTO mode, as desired. Operate unit for 15 minutes. Check system refrigerant charge.
SEQUENCE OF OPERATION
NOTE: Defrost control board is equipped with
With power supplied to indoor and outdoor units, transformer is energized.
Cooling
On a call for cooling, thermostat makes circuits
When thermostat is satisfied, its contacts open,
NOTE: If indoor unit is equipped with a
Heating
On a call for heating, thermostat makes circuits
Should temperature continue to fall,
5