Carrier 38YSA Required Liquid-LineTemperature F, Final Checks, Care And Maintenance

Models: 38YSA

1 12
Download 12 pages 12.23 Kb
Page 12
Image 12

Step 14— Final Checks

IMPORTANT: Before leaving job, be sure to do the following:

1.Securely fasten all panels and covers.

2.Tighten service valve stem caps to 1/12-turn past finger tight.

3.Leave User’s Manual with owner. Explain system operation and periodic maintenance requirements outlined in manual.

4.Fill out Dealer Installation Checklist and place in customer file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible equip- ment failure, periodic maintenance must be performed on this equipment.

Frequency of maintenance may vary depending upon geographic areas, such as coastal applications.

Table 3— Required Liquid-Line Temperature (° F)

LIQUID

 

REQUIRED SUBCOOLING

 

PRESSURE AT

 

 

TEMPERATURE

 

SERVICE VALVE

 

 

 

(° F)

 

(PSIG)

5

 

10

 

15

 

20

134

71

 

66

 

61

 

56

141

74

 

69

 

64

 

59

148

77

 

72

 

67

 

62

156

80

 

75

 

70

 

65

163

83

 

78

 

73

 

68

171

86

 

81

 

76

 

71

179

89

 

84

 

79

 

74

187

92

 

87

 

82

 

77

196

95

 

90

 

85

 

80

205

98

 

93

 

88

 

83

214

101

 

96

 

91

 

86

223

104

 

99

 

94

 

89

233

107

 

102

 

97

 

92

243

110

 

105

 

100

 

95

253

113

 

108

 

103

 

98

264

116

 

111

 

106

 

101

274

119

 

114

 

109

 

104

285

122

 

117

 

112

 

107

297

125

 

120

 

115

 

110

309

128

 

123

 

118

 

113

321

131

 

126

 

121

 

116

331

134

 

129

 

124

 

119

346

137

 

132

 

127

 

122

359

140

 

135

 

130

 

125

 

 

 

 

 

 

 

 

Copyright 2002 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231

38ysa4si

 

 

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 101

Catalog No. 533-80022

Printed in U.S.A.

Form 38YSA-4SI

Pg 12

02-02

Replaces: 38YSA3SI

 

Tab

5a

5a

 

 

 

 

 

 

 

Page 12
Image 12
Carrier 38YSA instruction manual Required Liquid-LineTemperature F, Final Checks, Care And Maintenance