Carrier 42 SERIES specifications Manufacturer

Models: 42 SERIES

1 32
Download 32 pages 42.35 Kb
Page 23
Image 23
MANUFACTURER

Table 1 Ð Acceptable Field-Furnished Pneumatic Valves

MANUFACTURER

VALVE NUMBER

TYPE

MODE

SIZE (in.)

CAPACITY

(OD Male Flare)

(CV) RATING

 

 

 

 

 

VP517A

3-WAY

MIXING

7¤8

3.0, 4.0, 6.3

 

VP522A&B

3-WAY

SEQUENCING

5¤8 or 7¤8

1.6/2.5 or 2.5/3.5/4.0

 

VP526A

3-WAY

MIXING

5¤8

1.6,

2.5

HONEYWELL

VP527A

2-WAY

N.O.

1¤2

0.63, 1.0, 1.6

 

VP513A

2-WAY

N.O.

5¤8 or 7¤8

2.5,

4.0

 

VP513B

2-WAY

N.C.

5¤8

1.0, 1.6, 2.5

 

VP531A

2-WAY

N.O.

5¤8 or 7¤8 (ODS)

1.6, 2.6, 3.3

 

V4332

3-WAY

MIXING

1¤2

1.2,

2.0

 

V4334

3-WAY

MIXING

5¤8

4.7

JOHNSON

V4440

3-WAY

SEQUENCING

1¤2

1.4,

2.4

SERVICE

V4440

3-WAY

SEQUENCING

5¤8

4.1,

4.7

 

V3766

2-WAY

N.O.

1¤2

1.0, 1.7, 3.2

 

V3966

2-WAY

N.C.

1¤2

1.7,

3.2

 

VK9312

3-WAY

MIXING

5¤8

2.0,

4.0

BARBER-

VK9332

3-WAY

SEQUENCING

5¤8

1.7, 2.4, 4.0

COLEMAN

VK9212

2-WAY

N.O.

5¤8

0.4, 1.3, 2.2, 3.3

 

VK9222

2-WAY

N.C.

5¤8

0.4, 1.3, 2.2, 3.3

 

VP656-0011, 10, 09

3-WAY

MIXING

1¤2

1.5, 2.5

 

VP658-0004, 5

3-WAY

DIVERTING

1¤2

2.5

MCC

VP658-0050, 51

3-WAY

SEQUENCING

1¤2

1.5, 2.5

POWERS

VP658-0004, 5

2-WAY

N.O.

1¤2

1.0, 2.5

 

VP656-0002, 4

2-WAY

N.O.

1¤2

0.9, 2.1

 

VP656-0012

2-WAY

N.C.

1¤2

2.1

 

2582 (V8200)

2-WAY

N.O.

1¤2

0.4, 0.6, 1.0, 1.6

 

2583 (V8300)

3-WAY

MIXING

1¤2

1.6

 

2561 (V6101)

2-WAY

N.C.

1¤2, 5¤8

1.2, 2.2, 4.1

ROBERTSHAW

2561 (V6102)

2-WAY

N.O.

1¤2

1.0, 1.6

2563 (V6300)

3-WAY

MIXING

1¤2

1.6

 

 

2563 (V6301)

3-WAY

MIXING

5¤8

2.5

 

2569 (V6900, 01)

3-WAY

SEQUENCING

1¤2, 5¤8, 7¤8

.6, 1.0, 1.1, 1.6,

 

2.5, 3.2, 2.4, 4.0, 4.5

 

 

 

 

 

CV

Ð See Note 5.

N.C.

Ð

Normally Closed

N.O.

Ð

Normally Open

OD

Ð Outside Diameter

NOTES:

1. This reference table lists valves that are acceptable because of capacity and piping connection type. Actual valve selection for spe-

ci®c mode (N.O. or N.C.) and capacity rating (C ) to meet jobsite

V

conditions must be made by ®eld personnel.

2.Valve size (1¤2-, 5¤8-, and 7¤8-in. OD) designates the matching tub- ing size.

Use price page package 18-2 or 18-4 for selecting 1¤2-in. or 5¤8-in. OD valves. Use price page package 18-3 or 18-5 for 7¤8-in. OD valves.

3.The 1¤2-in. and 5¤8-in. OD valves are used primarily on 42C (ceiling) and 42V (vertical) room fan coil units. The 7¤8-in. OD valves are recommended for use on 42D (ducted) units.

4.Flare connections are 45° SAE ¯are with body threaded for stand- ard ¯are nuts.

5.The CV capacity rating is the gpm ¯ow through a valve at 1.0 psi pressure drop.

EXAMPLE: A 2.5 CV valve has a ¯ow of 2.5 gpm at 1.0 psi pres- sure drop.

As ¯ow changes, pressure drop can be determined by the formula:

Actual gpm 2

P =

CV

6.Restrictions imposed by limited piping enclosures often require that the valve manufacturer's recommendation for obstruction free serv- ice clearances be waived. Service/isolation valves normally speci- ®ed will permit removal of the entire pneumatic valve for ®eld serv- ice if necessary.

7.Certain combinations of piping accessories and control valves have proven unacceptable in the past, therefore the factory must re- serve the right of review for ®nal acceptance.

8.Consult factory on all applications involving valves with thermo- static actuators or built in pneumatic thermostats.

23