Table 1 Ð Acceptable
MANUFACTURER | VALVE NUMBER | TYPE | MODE | SIZE (in.) | CAPACITY | ||
(OD Male Flare) | (CV) RATING | ||||||
|
|
|
| ||||
| VP517A | MIXING | 7¤8 | 3.0, 4.0, 6.3 | |||
| VP522A&B | SEQUENCING | 5¤8 or 7¤8 | 1.6/2.5 or 2.5/3.5/4.0 | |||
| VP526A | MIXING | 5¤8 | 1.6, | 2.5 | ||
HONEYWELL | VP527A | N.O. | 1¤2 | 0.63, 1.0, 1.6 | |||
| VP513A | N.O. | 5¤8 or 7¤8 | 2.5, | 4.0 | ||
| VP513B | N.C. | 5¤8 | 1.0, 1.6, 2.5 | |||
| VP531A | N.O. | 5¤8 or 7¤8 (ODS) | 1.6, 2.6, 3.3 | |||
| V4332 | MIXING | 1¤2 | 1.2, | 2.0 | ||
| V4334 | MIXING | 5¤8 | 4.7 | |||
JOHNSON | V4440 | SEQUENCING | 1¤2 | 1.4, | 2.4 | ||
SERVICE | V4440 | SEQUENCING | 5¤8 | 4.1, | 4.7 | ||
| V3766 | N.O. | 1¤2 | 1.0, 1.7, 3.2 | |||
| V3966 | N.C. | 1¤2 | 1.7, | 3.2 | ||
| VK9312 | MIXING | 5¤8 | 2.0, | 4.0 | ||
BARBER- | VK9332 | SEQUENCING | 5¤8 | 1.7, 2.4, 4.0 | |||
COLEMAN | VK9212 | N.O. | 5¤8 | 0.4, 1.3, 2.2, 3.3 | |||
| VK9222 | N.C. | 5¤8 | 0.4, 1.3, 2.2, 3.3 | |||
| MIXING | 1¤2 | 1.5, 2.5 | ||||
| DIVERTING | 1¤2 | 2.5 | ||||
MCC | SEQUENCING | 1¤2 | 1.5, 2.5 | ||||
POWERS | N.O. | 1¤2 | 1.0, 2.5 | ||||
| N.O. | 1¤2 | 0.9, 2.1 | ||||
| N.C. | 1¤2 | 2.1 | ||||
| 2582 (V8200) | N.O. | 1¤2 | 0.4, 0.6, 1.0, 1.6 | |||
| 2583 (V8300) | MIXING | 1¤2 | 1.6 | |||
| 2561 (V6101) | N.C. | 1¤2, 5¤8 | 1.2, 2.2, 4.1 | |||
ROBERTSHAW | 2561 (V6102) | N.O. | 1¤2 | 1.0, 1.6 | |||
2563 (V6300) | MIXING | 1¤2 | 1.6 | ||||
| |||||||
| 2563 (V6301) | MIXING | 5¤8 | 2.5 | |||
| 2569 (V6900, 01) | SEQUENCING | 1¤2, 5¤8, 7¤8 | .6, 1.0, 1.1, 1.6, | |||
| 2.5, 3.2, 2.4, 4.0, 4.5 | ||||||
|
|
|
|
|
CV | Ð See Note 5. | |
N.C. | Ð | Normally Closed |
N.O. | Ð | Normally Open |
OD | Ð Outside Diameter |
NOTES:
1. This reference table lists valves that are acceptable because of capacity and piping connection type. Actual valve selection for spe-
ci®c mode (N.O. or N.C.) and capacity rating (C ) to meet jobsite
V
conditions must be made by ®eld personnel.
2.Valve size
Use price page package
3.The
4.Flare connections are 45° SAE ¯are with body threaded for stand- ard ¯are nuts.
5.The CV capacity rating is the gpm ¯ow through a valve at 1.0 psi pressure drop.
EXAMPLE: A 2.5 CV valve has a ¯ow of 2.5 gpm at 1.0 psi pres- sure drop.
As ¯ow changes, pressure drop can be determined by the formula:
Actual gpm 2
P =
CV
6.Restrictions imposed by limited piping enclosures often require that the valve manufacturer's recommendation for obstruction free serv- ice clearances be waived. Service/isolation valves normally speci- ®ed will permit removal of the entire pneumatic valve for ®eld serv- ice if necessary.
7.Certain combinations of piping accessories and control valves have proven unacceptable in the past, therefore the factory must re- serve the right of review for ®nal acceptance.
8.Consult factory on all applications involving valves with thermo- static actuators or built in pneumatic thermostats.
23