PIPING COMPONENTS (cont)
SYMBOL/SKETCH | DESCRIPTION | CV FACTOR | RATING | STEAM | |||
1¤2 | 3¤4 | PSI | F | USE | |||
|
| ||||||
| STRAINER: |
|
|
|
|
| |
| 50 mesh stainless steel screen. |
|
|
|
|
| |
| Application - Used for removal of small |
|
|
|
|
| |
| particles from system water during |
|
|
|
|
| |
| normal system operation. Should not |
|
|
|
|
| |
| be used in lieu of main system | 9.0 | 19.0 | 400 | 250 | N/A | |
| strainers. Strainer screen may have to | ||||||
| Clean | Clean | |||||
| be removed during initial high pressure |
|
|
| |||
|
|
|
|
|
| ||
| system ¯ushing during |
|
|
|
|
| |
| Screen should be removed and cleaned |
|
|
|
|
| |
| per normal maintenance schedule |
|
|
|
|
| |
| (provisions for strainer |
|
|
|
|
| |
| not provided). |
|
|
|
|
| |
| GATE VALVE: Manual |
|
|
|
|
| |
| Application - Used for unit isolation | 19.8 | 36.0 | 200 | 200 | NO | |
| during system ¯ushing, servicing, etc. | ||||||
|
|
|
|
|
| ||
| Do not use for water balancing. |
|
|
|
|
| |
|
|
|
|
|
|
| |
| GLOBE VALVE: Standard pattern, |
|
|
|
|
| |
| manual |
|
|
|
|
| |
| Application - Used for unit isolation. | 1.8 | 3.9 | 200 | 200 | NO | |
| Not recommended for high ¯ow rates |
|
|
|
|
| |
| due to relatively high pressure drop. |
|
|
|
|
| |
| COMPRESSION STOP VALVE: |
|
|
|
|
| |
| Manual |
|
|
|
|
| |
| Application - Used for unit isolation | 2.3 | 5.4 | 150 | 200 | NO | |
| during system ¯ushing, servicing, etc. | ||||||
|
|
|
|
|
| ||
| Not recommended for high ¯ow rates |
|
|
|
|
| |
| due to relatively high pressure drop. |
|
|
|
|
| |
| BALL VALVE: Manual balance and |
|
|
|
|
| |
|
|
|
|
|
| ||
| Application - Used for unit isolation |
|
|
|
|
| |
| and water ¯ow balancing. Without | 4.0 | 7.5 | 400 | 200 | YES | |
| memory stop feature water balance | ||||||
| point must be marked by installer (if |
|
|
|
|
| |
| necessary). Check speci®cations for |
|
|
|
|
| |
| service ®ttings required when used for |
|
|
|
|
| |
| water balancing. |
|
|
|
|
| |
| BALL VALVE WITH MEMORY STOP: |
|
|
|
|
| |
| Manual balance and |
|
|
|
|
| |
| Application - Used for unit isolation |
|
|
|
|
| |
| and water ¯ow balancing. The adjust- | 4.0 | 7.5 | 400 | 200 | N/A | |
| able memory stop feature allows return | ||||||
| to the balance point after |
|
|
|
|
| |
| Check speci®cations for service |
|
|
|
|
| |
| ®ttings required when used for |
|
|
|
|
| |
| water balancing. |
|
|
|
|
|
26