Carrier 42 SERIES specifications PIPING COMPONENTS cont

Models: 42 SERIES

1 32
Download 32 pages 42.35 Kb
Page 26
Image 26
PIPING COMPONENTS (cont)

PIPING COMPONENTS (cont)

SYMBOL/SKETCH

DESCRIPTION

CV FACTOR

RATING

STEAM

1¤2

3¤4

PSI

F

USE

 

 

 

STRAINER: Y-type body with

 

 

 

 

 

 

50 mesh stainless steel screen.

 

 

 

 

 

 

Application - Used for removal of small

 

 

 

 

 

 

particles from system water during

 

 

 

 

 

 

normal system operation. Should not

 

 

 

 

 

 

be used in lieu of main system

9.0

19.0

400

250

N/A

 

strainers. Strainer screen may have to

 

Clean

Clean

 

be removed during initial high pressure

 

 

 

 

 

 

 

 

 

 

system ¯ushing during start-up.

 

 

 

 

 

 

Screen should be removed and cleaned

 

 

 

 

 

 

per normal maintenance schedule

 

 

 

 

 

 

(provisions for strainer blow-down

 

 

 

 

 

 

not provided).

 

 

 

 

 

 

GATE VALVE: Manual shut-off valve.

 

 

 

 

 

 

Application - Used for unit isolation

19.8

36.0

200

200

NO

 

during system ¯ushing, servicing, etc.

 

 

 

 

 

 

 

Do not use for water balancing.

 

 

 

 

 

 

 

 

 

 

 

 

 

GLOBE VALVE: Standard pattern,

 

 

 

 

 

 

manual shut-off and throttling valve.

 

 

 

 

 

 

Application - Used for unit isolation.

1.8

3.9

200

200

NO

 

Not recommended for high ¯ow rates

 

 

 

 

 

 

due to relatively high pressure drop.

 

 

 

 

 

 

COMPRESSION STOP VALVE:

 

 

 

 

 

 

Manual shut-off valve.

 

 

 

 

 

 

Application - Used for unit isolation

2.3

5.4

150

200

NO

 

during system ¯ushing, servicing, etc.

 

 

 

 

 

 

 

Not recommended for high ¯ow rates

 

 

 

 

 

 

due to relatively high pressure drop.

 

 

 

 

 

 

BALL VALVE: Manual balance and

 

 

 

 

 

 

shut-off valve.

 

 

 

 

 

 

Application - Used for unit isolation

 

 

 

 

 

 

and water ¯ow balancing. Without

4.0

7.5

400

200

YES

 

memory stop feature water balance

 

point must be marked by installer (if

 

 

 

 

 

 

necessary). Check speci®cations for

 

 

 

 

 

 

service ®ttings required when used for

 

 

 

 

 

 

water balancing.

 

 

 

 

 

 

BALL VALVE WITH MEMORY STOP:

 

 

 

 

 

 

Manual balance and shut-off valve.

 

 

 

 

 

 

Application - Used for unit isolation

 

 

 

 

 

 

and water ¯ow balancing. The adjust-

4.0

7.5

400

200

N/A

 

able memory stop feature allows return

 

to the balance point after shut-off.

 

 

 

 

 

 

Check speci®cations for service

 

 

 

 

 

 

®ttings required when used for

 

 

 

 

 

 

water balancing.

 

 

 

 

 