LEGEND For Fig. 1
Component Sizing Ð 1¤2 nominal (for 5¤8 OD copper tubing) or 3¤4 nominal (for 7¤8 OD copper tubing).
Manual Air Vent Ð Standard component - Brazed into high point of hydronic cooling and/or heating coil circuit.
Automatic Air Vent Ð Brazed into high point of coil circuit.
Coil Connections (Positions A & B) Ð When isolation valve only is added to supply or return line, the isolation valve will be factory brazed to the coil
STANDARD: Swage ®tting for ®eld braze.
OPTION: Union(s) added by factory for ®eld connection.
Service Fittings (Positions C & D) Ð Optional ®ttings for attaching pressure/temperature sensing devices to obtain pressure drop or temperature differential accross coil. Used with ball valve or balance valve where extremely accurate water ¯ow balancing is required.
GAGE COCK: Pressure test only - In supply and return lines.
PRESSURE TEST PORT: Pressure test only - In supply and return lines.
INSERTION TEST PORT: Pressure/Temperature test - In supply and return lines.
Water Flow Balancing (Positions E, F, & H) Ð Only one device per total valve package to be used for balancing water ¯ow through the coil. When isolation valve (ball valve or ball valve with memory stop at positionH) is used for water ¯ow balancing, do not specify additional balancing device at positionE or F. When balancing device is speci®ed at position E or F, isolation valve does not require balancing feature at position H (See exception,
CIRCUIT SETTER: May serve as a positive
BALANCING VALVE: Check speci®cations for service ®tting requirements.
FIXED FLOW: No balancing required - When there are more devices on the supply line of the valve package than on the return line, the factory may move this device to position E to ®t valve package within allotted space. Consult your factory representative to match the available ®xed ¯ow valve to your job requirements.
Strainer (Position G) Ð Does not include blow down ®tting and should not be used in lieu of main piping strainers.
Isolation Valves (Positions H & J) Ð Normally requires one each on supply and return line (see exception under circuit setter). When position H is used for balancing (ball vall or ball valve with memory stop), check speci®cations for service valve requirements.
GATE VALVE:
BALL VALVE:
BALL VALVE WITH MEMORY STOP:
17