![PIPING COMPONENTS](/images/new-backgrounds/33737/3373747x1.webp)
PIPING COMPONENTS
SYMBOL/SKETCH | DESCRIPTION | CV FACTOR | RATING | STEAM | |||
1¤2 | 3¤4 | PSI | F | USE | |||
|
| ||||||
| MANUAL AIR VENT: Threaded brass |
|
|
|
|
| |
| needle valve with screwdriver slot |
|
|
|
|
| |
| for adjustment. |
|
|
|
|
| |
| Application - Body brazed into high | N/A | N/A | 400 | 100 | NO | |
| point of heating and cooling coils for | ||||||
| bleeding air from coil. Standard item |
|
|
|
|
| |
| on all hydronic coils (not used on |
|
|
|
|
| |
| steam or DX coils). Should not be used |
|
|
|
|
| |
| in lieu of main system air vents. |
|
|
|
|
| |
| AUTOMATIC AIR VENT: Nickel |
|
|
|
|
| |
| plated brass valve, |
|
|
|
|
| |
| positive |
|
|
|
|
| |
| vent feature via knurled vent screw. |
|
|
|
|
| |
| Application - Optional replacement for |
|
|
|
|
| |
| manual air vent. Automatically passes |
|
|
|
|
| |
| minute quantities of air through the |
|
|
|
|
| |
| ®ber discs which expand upon contact | N/A | N/A | 125 | 240 | NO | |
| with water, completely sealing the | ||||||
|
|
|
|
|
| ||
| valve. As air accumulates, the ®ber |
|
|
|
|
| |
| discs dry and shrink, repeating the |
|
|
|
|
| |
| cycle. Not recommended for removing |
|
|
|
|
| |
| large quantities of air encountered |
|
|
|
|
| |
| during initial |
|
|
|
|
| |
| draining and re®lling. Should not be |
|
|
|
|
| |
| used in lieu of main system air vents. |
|
|
|
|
| |
| SWAGE: Copper tube end expanded |
|
|
|
|
| |
| to accept a copper tube of the same |
|
|
|
|
| |
| size for factory or ®eld brazing. |
|
|
|
|
| |
| Application - Used where possible for | N/A | N/A | 300 | 200 | YES | |
| all tubing joints for best joint integrity. | (*) | (*) | ||||
|
|
|
| ||||
| (*) See page 30 for ratings of different |
|
|
|
|
| |
| joining materials and operating |
|
|
|
|
| |
| temperatures. |
|
|
|
|
| |
| UNION: Combination wrought |
|
|
|
|
| |
| copper/cast brass union assembly, |
|
|
|
|
| |
| solder by solder. |
|
|
|
|
| |
| Application - Used for quick connect |
|
|
|
|
| |
| (and disconnect) of valve package | N/A | N/A | 300 | 200 | YES | |
| components to minimize ®eld labor | (*) | (*) | ||||
|
|
|
| ||||
| and facilitate servicing of unit. |
|
|
|
|
| |
| (*) See page 30 for ratings of different |
|
|
|
|
| |
| joining materials and operating |
|
|
|
|
| |
| temperatures. |
|
|
|
|
| |
| INSERTION TEST PORT: Brass body |
|
|
|
|
| |
| valve for acceptance of test probe (up |
|
|
|
|
| |
| to 1¤8 in. diameter). |
|
|
|
|
| |
| Application - Installed on one (or both) | N/A | N/A | 250 | 250 | NO | |
| sides of the coil to allow for temperature | ||||||
|
|
|
|
|
| ||
| or pressure sensing. Used for close |
|
|
|
|
| |
| tolerance water balancing and |
|
|
|
|
| |
| service analysis. |
|
|
|
|
|
24